(a) Where a potable water outlet terminates below the rim of a tank or vat and the tank or vat has an overflow of diameter not less than given in the following table, the overflow pipe shall be provided with an airgap as close to the tank as possible: TABLE II. SIZES OF OVERFLOW PIPES FOR WATER SUPPLY TANKS Maximum Capacity of Water Supply Line to Tank Diameter of Overflow Pipe (Inches ID) Maximum Capacity of Water Supply Line to Tank Diameter of Overflow Pipe (Inches ID) 0—50 gpm 2 400—700 gpm 5 50—150 gpm 21 /2 700—1,000 gpm 6 100—200 gpm 3 Over 1,000 gpm 8 200—400 gpm 4 (b) The potable water outlet to the tank or vat shall terminate a distance not less than 11 /2 times the height to which water can rise in the tank above the top of the overflow. This level shall be established at the maximum flow rate of the supply to the tank or vat and with all outlets except the airgap overflow outlet closed. (c) The distance from the outlet to the high water level shall be measured from the critical point of the potable water supply outlet.