Paulding County · Code of Ordinances
Part II - CODE OF ORDINANCES / Chapter 74 - WATER / Article II - CONTROL OF BACKFLOW AND CROSS CONNECTIONS
Sec. 74-46. Protective devices required.
About this text
- As published by Municode, current through 2025-12-09
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Approved devices to protect against backflow and backsiphonage shall be installed at all fixtures and equipment where backflow and/or backsiphonage may occur and where a minimum airgap cannot be provided between the water outlet to the fixture or equipment and its flood level rim.
(1) Connections not subject to backpressure. Where a water connection is not subject to backpressure, a vacuum breaker shall be installed on the discharge side of the last valve on the line serving the fixture or equipment. A list of some conditions requiring protective devices of this kind is given in Table A, Cross Connections Where Protective Devices are Required and Critical Level (C-L) Settings for Vacuum Breakers.
TABLE A CROSS-CONNECTION WHERE PROTECTIVE DEVICES ARE REQUIRED AND
CRITICAL LEVEL (C-L) SETTINGS FOR VACUUM BREAKERS
Fixture or Equipment Method of Installation Aspirators and ejectors C-L at least 6 inches above flood level of receptacle served.
Dental units On models without built-in vacuum breakers, C-L at least 6 inches above flood level rim of bowl.
Dishwashing machines C-L at least 6 inches above flood level of machine. Install on both hot and cold water supply lines.
Flushometers (closet and urinal) C-L at least 6 inches above top of fixture supplies.
Garbage can cleaning machines C-L at least 6 inches above flood level of machine. Install on both hot and cold water supply lines.
Hose outlets C-L at least 6 inches above highest point on hose line.
Laundry machines C-L at least 6 inches above flood level of machine. Install on both hot and cold water supply lines.
Lawn sprinklers C-L at least 12 inches above highest sprinkler or discharge outlet.
Steam tables C-L at least 6 inches above flood level.
Fixture or Equipment Method of Installation Tank and vats C-L at least 6 inches above flood level rim or line.
Trough urinals C-L at least 30 inches above perforated flush pipe.
Flush tanks Equip with approved ball cock. Where ball cocks touch tank water equip with vacuum breaker at least 1 inch above
overflow outlets. Where ball cock does not touch tank water, install ball cock outlet at least 1 inch above overflow outlet or provide vacuum breaker as specified above.
Hose bibbs (where aspirators or ejectors could be connected) C-L at least 6 inches above flood level of receptacle served.
a Critical level (C-L) is defined as the level to which the vacuum breaker may be submerged before backflow will occur. Where the C-L is not shown on the preventer, the bottom of the device shall be taken as the C-L.
(2) Connections subject to backpressure. Where a potable water connection is made to a line, fixture, tank, vat, pump, or other equipment with a hazard of backflow or backsiphonage where the water connection is subject to backpressure, and an airgap cannot be installed, the director may require the use of an approved reduced pressure principle backflow preventer. A partial list of such connections is shown in Table B.
TABLE B PARTIAL LIST OF CROSS-CONNECTIONS WHICH MAY BE SUBJECT TO
BACKPRESSURE
Chemical lines Pumps Dock water outlets Steam lines Individual water supplies Swimming pools Industrial process water lines Tank and vats — bottom inlets Pressure tanks Hose bibbs (Code 1987, § 5-135)
Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.