--- title: Rockdale County Code of Ordinances, Sec. 46-13. Fire protection sprinkler ordinance collection: local-codes id: local-code:rockdale-county/code/46-13 cite_as: Rockdale County, Ga., Code of Ordinances § 46-13 canonical_url: https://georgiacommons.org/counties/rockdale/code/46-13 md_url: https://georgiacommons.org/counties/rockdale/code/46-13.md text_url: https://georgiacommons.org/counties/rockdale/code/46-13/text source_url: https://library.municode.com/ga/rockdale_county/codes/code_of_ordinances date: 2026-01-27 status: active jurisdiction: county:rockdale jurisdiction_name: Rockdale County county_fips: "13247" corpus_version: local-codes-rockdale-county-c3e0b855bd42 publisher: Georgia Commons, an independent project of Georgia Civic Data. Not the State of Georgia. Not legal advice. up: https://georgiacommons.org/counties/rockdale/code/~part-ii/~part-a/~chapter-46/~article-ii.md previous: https://georgiacommons.org/counties/rockdale/code/46-12.md next: https://georgiacommons.org/counties/rockdale/code/46-14.md index: https://georgiacommons.org/counties/rockdale.md branch: code edition: As published by Municode, current through 2026-01-27 edition_date_kind: current_through source_publisher: Municode version_id: local-code:rockdale-county/code/46-13@2026-01-27-d020ef7c6e --- # Rockdale County Code of Ordinances, Sec. 46-13. Fire protection sprinkler ordinance > As published by Municode, current through 2026-01-27 > The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included. Part of: Part II - CODE OF ORDINANCES / Part A - GENERAL ORDINANCES / Chapter 46 - FIRE PREVENTION AND PROTECTION / Article II - FIRE PREVENTION (a) Hotels, motels, dormitories, lodging houses or rooming houses, residential board and care facilities, multifamily residential dwellings including townhomes and condominiums, educational occupancies, day care occupancies, and health care facilities, regardless of type of construction shall have complete, automatic fire sprinkler systems installed in accordance with NFPA installation standards. (b) All group home care occupancies must install a sprinkler system in accordance with NFPA 13R. (c) Assembly occupancies are required to install an automatic sprinkler system where one of the following conditions exist: (1) The building or space exceeds 5,000 square feet; (2) The building or space has an occupant load of 100 or more; (3) The building or space is located on a floor other than the level of exit discharge. (d) Multifamily dwellings up to and including three stories in height shall be sprinkled with an approved sprinkler system modified to include full sprinkler coverage in all attics and breezeways; (e) In addition to the NFPA Code any residential occupancies containing more than two dwelling units must install an approved automatic sprinkler system per NFPA 13, 13R, or 13D design requirements, as approved by the local fire marshal, including townhouses and condominiums. (1) Exception: Automatic residential sprinkler systems for townhouses shall be permitted to be designed and installed in accordance with NFPA 13D and shall be modified to include full sprinkler coverage in all attics and breezeways. (f) All buildings 6,000 square feet or more in an area under a common roof where vehicles are pulled inside for the purpose of maintenance, repair, storage, or installation of all accessories shall be fully sprinkled with an approved sprinkler system except where vehicle bay areas in a building are less than or equal to 600 square feet, it shall be permissible to place up to six sprinkler heads off of the domestic water supply in lieu of sprinkling the entire building. In so doing, calculations must be performed by an approved sprinkler contractor certified by the State of Georgia and such calculations must be shown on the plans submitted for approval by the fire marshal's office. (g) Each automatic sprinkler system required by this article shall be in accordance with one of the following: (1) NFPA 13, Standard for the Installation of Sprinkler Systems. (2) NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and TwoFamily Dwellings and Manufactured Homes. (3) NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height. (h) All buildings or structures installing a 13R sprinkler system must also install a sprinkler system in the attic. (1) Exception: Paragraphs (a) through (h); plans submitted prior to adoption of the ordinance from which this article is derived, must meet the sprinkler requirements adopted at the time plans were submitted. (i) To provide enhanced fire safety and protection, a "fire wall" shall not be considered to be a separate building so as to avoid the required automatic fire extinguishing system requirements. (j) Approved ventilation hoods and hood fire suppression equipment shall be installed in restaurants or other occupancies, including food trucks, with food preparation facilities having cooking appliances capable of producing grease laden vapors, such as ranges, deep fat fryers, grills, broilers, or other similar appliances. The standards for approval of such facilities shall be based on the fire code, including NFPA 96, Ventilation Control and Fire Suppression of Commercial Cooking Operations. (k) Buildings shall be equipped with an approved standpipe system when required by the building or fire code. Required standpipes shall be installed in accordance with the building code, fire code, and NFPA 14, Installation of Standpipe and Hose Systems. Site plans with fire hydrant and FDC location must be submitted for review by the local fire marshal, prior to installation. (l) The fire department connection (FDC) must be placed at the main entrance (driveway), or as approved by the AHJ and out of the collapse zone of the building with no obstructions, and within 50 feet of a fire hydrant. The FDC should stand between 36 inches to 48 inches above grade. No person shall put any post or installation or structure or landscaping closer than 36 inches to any fire department connection (FDC) or hydrant or visibly obstruct the view of the FDC from the entrance. (m) Before any fire protection system is installed, plans shall be submitted by the contractor installing the sprinkler system to the fire marshal's office, which shall review the plans for compliance with NFPA standards prior to stamping the plans as "reviewed." Plans must show: (1) Proposed system design over building layout. (2) Copy of Georgia State License. (3) All sets of working plans shall be signed and a certified seal placed thereon. (4) Hydraulic calculations. Information sheets (cut sheets) on materials. (n) Sprinkler system installers, inspectors, and maintenance personnel shall meet the Rules and Regulations for Enforcement of the Georgia Fire Sprinkler Act, [Ga. Comp. R. & Regs. R.] 120-3-19. (o) The responsibility for annual testing and maintenance of any fire protection system is the responsibility of the owner of the property. Systems shall be inspected and tested in accordance with NFPA 13, 13D, or 13R, NFPA 25 and the manufacture's requirements. (p) All automatic sprinkler equipment shall always be in proper operating conditions. The occupant of the building containing such equipment shall promptly notify the fire marshal or the county fire department in case such sprinkler protection is withdrawn, interrupted, curtailed, or altered. ## History (Ord. No. O-2025-16, § 4, 7-8-2025)