Sec. 98-170. High strength wastewater surcharge.

About this text

  • As published by Municode, current through 2026-01-27
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) Establishment. All users discharging high strength wastewater into the county wastewater system shall be assessed a monetary surcharge, in addition to the normally required wastewater use charges, in an amount to be calculated as shown in this section. A high strength wastewater is defined as wastewater which contains the following parameters in excess of the concentrations shown as follows:

(1) Five-day, 20 degrees Celsius biochemical oxygen demand of 225 milligrams per

liter (mg/l);

(2) Total suspended solids of 225 mg/l;

(3) Total ammonia nitrogen (NH3+NH4) of 20 mg/l;

(4) Total inorganic phosphates of 10 mg/l;

(5) Floatable oil and grease of 100 mg/l.

The parameters in this subsection shall be determined by the utilization of the sampling and testing procedures as provided in section 98-164. The amount of the surcharge, which is charged and assessed against all users discharging high strength wastewater into the county wastewater system, shall reflect the cost incurred by the county in handling the excess BOD, TSS, ammonia, total inorganic phosphates, and floatable oil and grease.

This surcharge shall include a proportionate share of charges for maintenance and operation of the wastewater treatment facilities including depreciation and other incidental expenses.

(b) Formula. When the concentrations of the surcharged parameters exceed the values of the constituents as set forth in subsection (a) of this section, the excess concentrations shall be subject to a surcharge in the amount derived in accordance with the following formula:

P × (D) × 8.34 × C=$/month Where:

P is equal to the concentration in mg/l of the parameter being evaluated (BOD, TSS,

ammonia, total inorganic phosphates, or floatable oil and grease) which is in excess of the amounts shown in subsection (a) of this section.

D is equal to the average daily wastewater discharge as determined by the county in subsection (d) of this section, or at the discretion of the county by variable periodic compliance reports as required in section 98-166.

8.34 is a conversion factor.

C is equal to the unit cost in dollars per pound ($/lb) for the treatment of the surcharged parameters. This value shall be established by the department manager based on actual wastewater treatment costs which shall be revised from time to time as necessary.

(c) Quantitative measurement of surchargable parameters. The measurement of the surcharge parameters (BOD, TSS, ammonia, total inorganic phosphates, or floatable oil and grease) shall be conducted as follows:

(1) The county shall sample and test the user as provided in section 98-164 once

per year, except that the duration of the sampling to determine surcharge shall

be for a period to be determined by the director of the department of water resources.

(2) The county need not provide any prior notice to the industry with regard to the sampling period.

(3) The county may sample the user as often as desired at the county's expense if, in the opinion of the county representative, samples have not been previously

obtained.

(4) If in the opinion of the user the samples taken by the county are not representative of the user's typical wastewater, then the user may request a resampling.

At the user's request, the county shall grant the user not more than two resamplings per year. All user-requested resampling shall be done at the user's expense.

A reasonable cost shall be charged to the user by the county therefor.

(d) Measurement of flow used in computing wastewater surcharges. The volume of flow used in computing wastewater surcharges shall be based upon the average daily flow rate as determined by county personnel using a properly maintained and calibrated flow meter during the sampling period outlined in subsection (c)(1) of this section.

(e) Billing procedure. Wastewater surcharges as provided for in this section shall be included on the user's regular water and wastewater bill or on a separate wastewater surcharge bill.

(Ord. No. 2007-07, § 1, 3-27-2007; Ord. No.

2016-15, § 1, 10-11-2016)

Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.

Version local-code:rockdale-county/code/98-170@2026-01-27-18ba7882e7

The assistant can say what this section says in this edition, quoting it and linking to it. It will not apply the law to your situation, and nothing here is legal advice.