Skip to content
Georgia Commons
Menu

Rockdale County · Code of Ordinances

Part II - CODE OF ORDINANCES / Part A - GENERAL ORDINANCES / Chapter 98 - UTILITIES / Article II - WATER SYSTEM / Division 2 - CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION

Sec. 98-59. Backflow prevention and cross connection control required.

About this text

  • As published by Municode, current through 2026-01-27
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

The department shall not allow, install or maintain any water service connection to the county's system to any premises unless the water supply is protected from potential backflow and cross connection as required by the laws of the State of Georgia, the Rules of the Georgia

Environmental Protection Division, the State of Georgia Plumbing Code and this division. An approved backflow prevention assembly shall be installed on each service line to a customer's system immediately downstream of the water meter or as close as physically feasible to the water meter. No backflow prevention assembly other than as specified in this section shall be allowed, installed or maintain without the express written approval of the director. If, in the judgment of the director, an approved backflow prevention assembly is required at either the customer's water service connection or within the customer's

private water system for the safety of the county's system, the director shall give written notice said customer to install such an approved backflow prevention assembly(s) at a specific location(s) on his premises. The director's judgment shall be based on the rules and on all policies

that the county may adopt to implement this division.

Within 30 days after receipt of written notice from the director that installation of cross connection protection or backflow prevention assemblies is required, a customer shall install

such approved protection or assemblies at the customer's sole expense.

In all cases, a backflow prevention assembly shall be installed before the first branch line leading off the service line wherever the following conditions exist:

(1) In the case of premises having an auxiliary water supply which is not or may not be of safe bacteriological or chemical quality and which is not acceptable as an additional source by the department, the public water system shall be protected against backflow from the premises by installing an approved air gap or an approved reduced pressure principle backflow prevention assembly in the service line commensurate with the degree of

hazard.

(2) In the case of premises on which any industrial fluids or any other objectionable substance are handled in such a fashion as to create an actual or potential

hazard to the public water system, the public system shall be protected against backflow from the premises by installing an approved backflow prevention assembly in the service line commensurate with the degree of hazard. This shall include the handling of process waters and waters originating from the water purveyor's system which have been subject to deterioration in quality.

(3) In the case of premises having (1) internal cross connections that cannot be permanently corrected or protected against, or (2) intricate plumbing and piping arrangements or where entry to all portions of the premises is not readily accessible for inspection purposes, making it impracticable or impossible to ascertain whether or not dangerous cross connections exist, the public water system shall be protected against backflow from the

premises by installing an approved backflow prevention assembly in the service line.

(4) In the case of any premises where there is pollution or polluted water that would be objectionable but not hazardous to health, if introduced into the public water system, the public water system shall be protected by an approved double check valve backflow prevention assembly.

(5) In the case of any premises where there is any contamination which is handled in such a fashion as to create an actual or potential hazard to the public water system, the public water system shall be protected by an approved air gap or an approved reduced pressure principle backflow prevention assembly. Examples of premises where these conditions will exist

include sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries and plating plants.

(6) In the case of any premises where there are actual or potential unprotected cross connections, the public water system shall be protected by an approved backflow prevention assembly at the water service connection.

(7) In the case of any premises where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete in-plant

cross-connection survey, the public water system shall be protected against backflow from the premises by either an approved air gap or an approved reduced

pressure principle backflow prevention assembly on each water service connection to the premises.

History

The history line the source prints at the end of the section.

(Ord. No. 2007-07, § 1, 3-27-2007)

Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.

Version local-code:rockdale-county/code/98-59@2026-01-27-2abbb7f850

The assistant can say what this section says in this edition, quoting it and linking to it. It will not apply the law to your situation, and nothing here is legal advice.