Union County · Code of Ordinances
Part II - CODE OF ORDINANCES / Chapter 18 - BUILDINGS AND BUILDING REGULATIONS / Article IV - STANDARD CODES / Division 2 - ADMINISTRATION AND ENFORCEMENT
Sec. 18-111. Multi-family dwellings installation of hydrants.
About this text
- As published by Municode, current through 2023-11-30
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) Jurisdiction. This article shall apply to all complexes utilizing a public water system subsequent to January 2020.
(b) Standards for installation of hydrants. All expansions of public water lines within Union County shall include the provision of hydrants in accordance with the following standards:
(1) Hydrant number, locations, and spacing shall be in accordance with the 2018 International Fire Code Appendix C - Fire Hydrant Locations and Distribution. Fire Flow requirement shall also be in accordance with the 2018 International Fire Code Appendix B.
(2) All hydrants shall stand plumb and be set with the lowest outlet of the hydrant not less than 18 inches above grade.
(3) Each hydrant shall be equipped with two-and-one-half-inch outlets and a steamer port with four-and-one-half-inch outlet National Standard Thread.
(4) The steamer port shall face the street. Where the street cannot be clearly defined, the fire authority will determine the appropriate alignment of the ports.
(5) There shall be a cleared and level area around the hydrant with a minimum radius of 36 inches.
(6) Hydrants shall not be obstructed by any structure or vegetation that would impair sight visibility of the hydrant within a distance of 150 feet in any direction of vehicular approach to the hydrant.
(Ord. of 06-01-2021(1)) Secs. 18-112—18-130. Reserved.
Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.