(a) The National Electrical Code, adopted in section 22-61, is amended as follows: Article 230-90(a), exception no. 3 is deleted in its entirety. Article 310-5 is amended so that conductors, whether solid or stranded, shall not be smaller than no. 12. Structures which require branch circuits to be installed within that structure, those circuits (located on the load side of the main breaker) shall be wired in copper except for all 220 volt circuits, other than window air conditioning units. Aluminum conductors where allowed shall be no smaller than 6. (b) The code is further amended as follows: (1) The electrical service including the main breaker box for all structures shall be a minimum of 100 amperes; (2) The electric service entrance installed in any building shall be at least 100 amperes per building unit, except that in a multiunit residential apartment building with a central laundry room, the electric service entrance may be 60 amperes per residential unit; and (3) The ground wire shall be a minimum of no. 6 on 100 amperes service, a minimum of no. 4 on 150 amperes and 200 amperes service.