Sec. 18-32. Fire hydrants.
About this text
- As published by Municode, current through 2026-07-09
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
As referenced in section 18-65, State minimum fire safety standards, adopted, incorporated by reference;
amendments, the International Fire Code (IFC) is incorporated by reference. IFC outlines fire protection systems and appliances public and private. County ordinance requires the following in addition to those requirements of the IFC.
(1) Fire hydrant installation. Fire hydrants installed in the County shall meet ANSI/AWWA C502 standards, ISO standards, and have a minimum of 1 5-inch Storz connection, and 2 21
/2-inch connections. All fire hydrants installed in the County shall be approved by the Fire Official. Fire hydrants without a pumper connection shall not be permitted. All hydrant cut-off valves shall be accessible and readily identified.
Hydrant cut-off valves shall be located within a 3-foot radius of the fire hydrant it serves unless otherwise authorized by the Fire Official or Water Department Official.
(2) Fire hydrant specification. Current specifications for fire hydrants must be obtained from the Fire Marshal's Office prior to installation.
(3) Water supply. Adequate water supply to meet a minimum needed fire flow (NFF) as defined by ISO (Insurance Services Office) shall be provided for all buildings constructed within the County. To ensure an adequate water supply exists, all proposed developments shall supply to the Fire Department a 24-hour water study by an independent third party. The study shall be of the immediate adjacent property to the proposed development including fire hydrant flow tests. More capacity may be required under certain circumstances by the Fire Official. Water mains, appliances, and fire hydrants shall be installed to provide the NFF or available water whichever is greater. In all cases, it is the responsibility of the property owner or developer to provide everything needed in order to provide the NFF or available water for fire protection. All fire flow tests shall be witnessed by the Fire Official, or representative, prior to final approval. Dead-end water mains shall be avoided when at all possible. All water mains shall be part of a grid, or loop, system to provide for the use of more than 1 hydrant at a time.
a. The needed fire flow for fire protection shall be determined by an approved method by the Fire Department having jurisdiction. The needed fire flow will be determined before construction commences.
b. Multiple fire hydrants may be required to produce the needed fire flow as required by ISO (Insurance Services Office). For each 1,000 gallons per minute (GPM) flow determined for a property, an additional fire hydrant will be required to be installed. The need for additional fire hydrants will be determined before construction commences.
c. If a building's needed fire flow is determined to be more than 2,650 GPM, the building shall be protected by a full sprinkler system. The sprinkler system must be installed and maintained by a State of Georgia certified fire protection sprinkler contractor as defined in the Rules and Regulations of the Safety Fire Commissioner, Ga. Comp. Rules and Regs. ch. 120-3-19 titled, Rules and Regulations for Enforcement of the Georgia Fire Sprinkler Act. The sprinkler system must be inspected as required by the NFPA (National Fire Protection Association) for the entire life of the building regardless of a change in ownership or occupancy classification.
d. The minimum acceptable fire hydrant test for residential areas shall be 500 GPM flow with 20 PSI residual pressure.
(4) Locations of fire hydrants. Commercial, industrial, institutional, and other similar type building shall have a maximum distance from the nearest hydrant to the most remote exterior point of any building of 300 feet. The maximum distance may be increased to 1,000 feet for those one- and two-family dwellings determined by the Fire Official to be located in a predominately residential area. For every 1,000 GPM of the needed fire flow, an additional hydrant shall be installed. All hydrants need to meet the building's NFF. All hydrants must be installed within 1,000 feet of the building. The distance should be measured on a roadway surface meeting the Fire Department access requirements outlined in the IFC, with distance being added for turns and obstacles that may increase the way hose may be laid.
(5) Water main sizes. Capable of delivering the required fire flow shall be as follows:
a. One- and two-family residential areas (excluding apartments and town houses) shall be supplied by a minimum 6-inch water main.
b. Commercial business areas (including apartments and townhouses) shall be supplied by a minimum 8-inch water main.
c. Industrial business areas shall be supplied by a minimum 10-inch water main.
(6) Obstruction. It shall be unlawful for any person to obstruct or hinder the approach of the Fire Department to any fire hydrants. In order to ensure access to fire hydrants, the following requirements must be met:
a. A minimum of 36 inches of clearance is required around a fire hydrant;
b. No person or entity shall construct any fence or other structure which would encroach the 36-inch minimum clearance for fire hydrants as outlined in subsection (6)a of this section and no fence shall be constructed between the fire hydrant and the roadway;
c. Fire hydrants shall not be buried, caps shall be at least 12 inches from grade;
d. No person shall allow trees, bushes, or other growth upon the person's property to interfere with the approach to any fire hydrant or to encroach the 36-inch minimum clearance;
e. A fire hydrant may not be painted except by an authorized agent or employee of the Fire Department of the County; and
f. Parking of motor vehicles within 15 feet of a fire hydrant is prohibited. Parking lot lines may be required, as necessary.
(7) Exceptions. Exceptions to the above shall be other installations acceptable to and approved by the authority having jurisdiction.
a. Any new construction development unable to comply with the NFF due to lack of infrastructure of the water system shall obtain an alternative method engineered and presented for approval.
b. Residences over 5,000 square feet in remote areas of the County or residences that have a NFF of over 2,650 GPM will require a residential sprinkler system; this shall include areas with driveways not accessible by fire suppression apparatus.