In all areas of special flood hazard where base flood elevation data has been provided, the following provisions are required: (1) Residential construction. New construction or substantial improvement of any residential dwelling (or manufactured home) shall have the lowest floor, including basement, elevated no lower than two feet above the base flood elevation. Electrical, heating, ventilation, plumbing, air conditioning equipment, and other service facilities are included as being part of the lowest floor. Should solid foundation perimeter walls be used to elevate a structure, openings sufficient to facilitate the unimpeded movements of flood waters shall be provided (see subsection (3) for minimum requirements). (2) Nonresidential construction. New construction or substantial improvement of any commercial, manufacturing, or nonresidential building or structure shall have the lowest floor, including basement, elevated no lower than two feet above the level of the base flood elevation. Electrical, heating, ventilation, plumbing, air conditioning equipment, and other service facilities are included as being part of the lowest floor. Buildings located in all "A" zones may be floodproofed in lieu of being elevated provided that all areas of the building below the required elevation are watertight with walls substantially impermeable to the passage of water, and use structural components having the capability of resisting hydrostatic and hydrodynamic loads and the effect of buoyancy. For floodproofing the minimum limit above the base flood elevation is doubled from two to four feet. A registered professional engineer or architect shall certify that the standards of this subsection are satisfied. (3) Elevated buildings: New construction or substantial improvements of elevated buildings which include fully enclosed areas formed by foundation and other exterior walls below the base flood elevation shall be designed to preclude finished living space and designed to allow for the entry and exit of floodwaters automatically to equalize hydrostatic flood forces on exterior walls. Designs for complying with this requirement must either be certified by a professional engineer or architect, or shall meet the following minimum criteria: (a) Provide a minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding. 1. Provide a minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding. 2. The bottom of all openings shall be no higher than one foot above grade. 3. Openings may be equipped with screens, louvers, valves or other coverings or devices provided they permit the automatic flow of floodwaters in both directions. (b) Access to the enclosed area shall be the minimum necessary to allow for parking of vehicles (garage door) or limited storage of maintenance equipment used in connection with the premises (standard exterior door) or entry to the living area (stairway or elevator). (c) The interior portion of such enclosed area shall not be partitioned or finished into separate rooms.