Sec. 10-146. Heating.
About this text
- As published by Municode, retrieved 2026-11-23
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) The construction and installation of the heating appliances shall be such that all of the flue gases shall be carried to the outside of the building through the flue outlet.
(b) Unvented combustion type heaters shall not be used.
(c) All automatic natural gas heating equipment shall be equipped with automatic safety pilot. All liquefied petroleum gas burning appliances shall be equipped with 100 percent safety cut-off pilot.
(d) Gas water heaters shall not be installed in bathrooms and bedrooms or closets connected thereto.
(e) Each gas-fired heating unit shall be inspected at least annually by a qualified heating contractor before its use at the onset of cool weather. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and or correction of any deficiency.