CAMDEN COUNTY, GEORGIA BOARD OF COUNTY COMMISSIONERS WORK SESSION APRIL 21, 2026, 5:00 PM Present: Chairman Robbie Cheek; Vice-Chairman Martin Turner; Commissioner Ben L. Casey; Commissioner Jim Goodman;; Commissioner Cody Smith; Interim County Administrator Joey Yacobacci, Interim Deputy County Administrator Shannon Nettles County Clerk Katie Bishop; Deputy County Clerk Shekia Robinson; and County Attorney Jacqueline Fortier. Chairman Cheek called the Work Session to order at 5:00 p.m. Work Session – Discussion regarding an Ordinance to Amend the Camden County Unified Development Code; to Establish Regulations Governing Data Centers; to Provide for Definitions, Permitted Uses, Development Standards, Performance Criteria, and Application Requirements; to provide for Severability; to Repeal Conflicting Ordinances; and for other purposes. At this time, Interim Planning Director Cassie Turpin presented a PowerPoint overview of the Ordinance to Amend the Camden County Unified Development Code; to Establish Regulations Governing Data Centers; to Provide for Definitions, Permitted Uses, Development Standards, Performance Criteria, and Application Requirements; to provide for Severability; to Repeal Conflicting Ordinances; and for other purposes. ° WHAT ARE DATA CENTERS AND > WHY ARE THEY IN SUCH HIGH ~ DEMAND? WHAT IS IT: A BUILDING OR FACILITY HOUSING INFASTRUCTURE FOR DATA STORAGE, PROCESSING AND OTHER RELATED DIGITAL SERVICES. WHY ARE THEY IN DEMAND: DUE TO THE INCREASE IN DATA GENERATION AND CONSUMPTION FROM ARTIFICIAL INTELLIGENCE, DATA ANALYTICS, CLOUD COMPUTING, ETC. AMENDMENT TO ARTICLE 2 (SUMMARY TABLE) SEC. 228 — TABLE 2.2: ALLOWED LAND USES BY ZONING DISTRICT AMEND “DATA PROCESSING, HOSTING AND RELATED SERVICES” AS FOLLOWS: CURRENT USE - NAICS CODE 518 — USE DATA PROCESSING, HOSTING AND RELATED SERVICES ALLOWED BY RIGHT IN C-G, I-R & I-G NEW DIVISION IN ARTICLE 3 (RESTRICTIONS ON PARTICULAR USES) ARTICLE 3 — DIVISION 5 — DATA CENTERS: NEW SECTION - SEC. 332 — DATA CENTERS THE PROVISIONS OF THIS SECTION SHALL APPLY TO ALL DATA CENTERS AND DATA CENTER CAMPUSES, INCLUDING EXPANSIONS OF EXISTING FACILITIES, WITHIN THE UNINCORPORATED AREA OF CAMDEN COUNTY. SEC. 332 (A) PURPOSE. THE PURPOSE OF THIS DIVISION IS TO ESTABLISH GUIDELINES AND REGULATE THE USE OF ALL DATA CENTERS AND DATA CENTER CAMPUSES. THE GOALS OF THIS DIVISION ARE: ESTABLISH CLEAR DEFINITIONS AND CLASSIFICATIONS FOR DATA CENTER USES; LIMIT DATA CENTER DEVELOPMENT TO APPROPRIATE ZONING DISTRICTS; PROTECT GROUNDWATER AND SURFACE WATER RESOURCES THROUGH CONSERVATION-ORIENTED STANDARDS; ENSURE ADEQUATE UTILITY CAPACITY; MINIMIZE ADVERSE NOISE, VISUAL, AND ENVIRONMENTAL IMPACTS; PROMOTE SUSTAINABLE DESIGN, ENERGY EFFICIENCY, AND RESPONSIBLE LONG- TERM OPERATION; AND ENSURE THAT DATA CENTER DEVELOPMENT OCCURS IN A MANNER CONSISTENT WITH THE PUBLIC INTEREST AND THE LONG-TERM GOALS OF CAMDEN COUNTY. SEC. 333 — DEFINITIONS RELATED TO DATA CENTERS * Closed-Loop Cooling System HYPERSCALE DATA CENTER Data Center LOAD * Data Center, Minor * Data Center, Medium MEGAWATT (MW) ¢ Data Center, Major SUBSTATION * Data Center Campus WATER CONSERVATION PLAN SEC. 334 — GENERAL PROVISIONS (A) PERMITTED ZONING DISTRICTS. 1. DATA CENTERS SHALL BE PERMITTED ONLY UPON SPECIAL USE APPROVAL IN THE INDUSTRIAL RESTRICTED (I-R) AND INDUSTRIAL GENERAL (I-G) ZONING DISTRICTS. - DATA CENTERS SHALL NOT BE PERMITTED AS A USE BY RIGHT. SEC. 334 —- GENERAL PROVISIONS (CONTINUED) (B) — PROHIBITED LOCATIONS DATA CENTERS SHALL BE PROHIBITED: - IN RESIDENTIAL, AGRICULTURAL, AND COMMERCIAL ZONING DISTRICTS; - WITHIN FEMA-DESIGNATED FLOODWAYS; . WITHIN COASTAL HIGH HAZARD AREAS (V- ZONES AND COASTAL A (LIMWA)); - ON BARRIER ISLANDS OR ENVIRONMENTALLY SENSITIVE COASTAL LANDS. SEC. 334 — GENERAL PROVISIONS (CONTINUED) (C) — DEVELOPMENT STANDARDS (1) MINIMUM LOT SIZE A. THE MINIMUM LOT SIZE FOR DATA CENTERS WITH LESS THAN 100,000 SQUARE FEET OF GROSS FLOOR AREA SHALL BE 50 ACRES. ~ THE MINIMUM LOT SIZE FOR DATA CENTERS WITH MORE THAN 100,000 SQUARE FEET OF GROSS FLOOR AREA SHALL BE 200 ACRES. SEC. 334 — GENERAL PROVISIONS (CONTINUED) (C) — DEVELOPMENT STANDARDS (2) SETBACKS AND HEIGHT RESTRICTIONS A. MINIMUM FRONT YARD SETBACK FROM PROPERTY LINE SHALL BE 150 FEET. MINIMUM SIDE YARD SETBACK FROM PROPERTY LINE SHALL BE 200 FEET. B C. MINIMUM REAR YARD SETBACK FROM PROPERTY LINE SHALL BE 200 FEET. D MAXIMUM BUILDING HEIGHT SHALL NOT EXCEED 70 FEET. SEC. 334 — GENERAL PROVISIONS (CONTINUED) (C) — DEVELOPMENT STANDARDS (3) BUFFERS AND SEPARATION A. DATA CENTERS SHALL MAINTAIN A 500-FOOT BUFFER FROM RESIDENTIALLY ZONED PROPERTY LINES. . DATA CENTER SHALL NOT BE LOCATED WITHIN 1,000 FEET OF ANY EXISTING RESIDENTIAL STRUCTURE. . REQUIRED BUFFERS SHALL BE MEASURED FROM THE DATA CENTER PROPERTY LINE TO THE ADJACENT PROPERTY LINE AND SHALL REMAIN UNDISTURBED EXCEPT FOR APPROVED LANDSCAPING, SCREENING, OR STORMWATER FEATURES. . REQUIRED BUFFERS SHALL INCLUDE LANDSCAPED AREAS AND SOLID WALLS OR BERMS DESIGNED TO PROVIDE VISUAL SCREENING AND SOUND ATTENUATION. SEC. 334 — GENERAL PROVISIONS (CONTINUED) (D) OPERATIONAL STANDARDS (1) NOISE MEASUREMENT STANDARDS A. MAXIMUM LEVELS AT RESIDENTIAL PROPERTY LINE: 1. 60 DB(A) DAYTIME 7:00 AM TO 6:00 PM 2. 50 DB(A) NIGHTTIME 6:00 PM TO 7:00 AM B. NOISE LEVELS SHALL BE MEASURED: 1. USING ANSI OR ISO-RECOGNIZED SOUND MEASUREMENT STANDARDS; 2. BY A QUALIFIED ACOUSTICAL PROFESSIONAL OR LICENSED ENGINEER; AND 3. DURING NORMAL FACILITY OPERATIONS, EXCLUDING FORCE MAJEURE EVENTS OR EMERGENCY CONDITIONS. C. GENERATOR TESTING: 1. EMERGENCY GENERATORS SHALL COMPLY WITH ALL APPLICABLE EPA EMISSIONS STANDARDS AND SHALL BE USED ONLY FOR EMERGENCY OPERATIONS, UTILITY OUTAGES, OR ROUTINE TESTING. ROUTINE TESTING SHALL OCCUR ONLY BETWEEN 7:00 AM AND 6:00 PM, SHALL NOT EXCEED 8 TOTAL HOURS PER CALENDAR MONTH PER SITE, AND SHALL BE CONDUCTED IN A MANNER THAT MINIMIZES NOISE IMPACTS TO ADJACENT PROPERTIES. THE PLANNING DIRECTOR OR DESIGNEE MAY REQUIRE ADVANCE NOTIFICATION OF ROUTINE TESTING SCHEDULES FOR FACILITIES LOCATED WITHIN 500 FEET OF RESIDENTIAL ZONING DISTRICTS. SEC. 334 — GENERAL PROVISIONS (CONTINUED) (D) OPERATIONAL STANDARDS (2) LIGHTING MAXIMUM LEVELS AT RESIDENTIAL PROPERTY LINE: A. FULL CUT-OFF FIXTURES SHALL BE REQUIRED. B. MAXIMUM 0.05 FOOTCANDLES SHALL BE ALLOWED AT RESIDENTIAL PROPERTY LINES. SEC. 334 — GENERAL PROVISIONS (CONTINUED) (D) OPERATIONAL STANDARDS (3) WATER AND COOLING SYSTEMS A. OPEN-LOOP COOLING SYSTEMS SHALL BE PROHIBITED B. ALL COOLING AND VENTILATION SYSTEMS SHALL UTILIZE CLOSED-LOOP SYSTEMS C. PRIOR TO CONSTRUCTION OR OCCUPANCY, ANY APPLICANT PROPOSING GROUNDWATER OR SURFACE WATER WITHDRAWALS IN EXCESS OF 100,000 GALLONS PER DAY SHALL PROVIDE PROOF OF A VALID GEORGIA ENVIRONMENTAL PROTECTION DIVISION (EPD) WATER USE PERMIT, INCLUDING AN APPROVED WATER CONSERVATION PLAN WHERE REQUIRED. PROOF OF APPLICATION AND A COPY OF ALL PERMIT CONDITIONS MUST BE SUBMITTED TO THE COUNTY BEFORE ANY GRADING, BUILDING PERMIT, OR CERTIFICATE OF OCCUPANCY IS ISSUED. D. FACILITIES PROPOSING GROUNDWATER OR SURFACE WATER WITHDRAWALS IN EXCESS OF 100,000 GALLONS PER DAY MUST DEMONSTRATE THAT WATER USE IS MINIMIZED AND THAT ANY CONSUMPTIVE USE IS MITIGATED (E.G., REUSE, RETURN TO SOURCE, CLOSED-LOOP SYSTEMS). E. IF THE PROJECT SITE IS WITHIN THE COASTAL PERMITTING PLAN AREA, APPLICANTS SHALL DOCUMENT COMPLIANCE WITH APPLICABLE COASTAL WATER CONSERVATION CONDITIONS ADOPTED UNDER THE GEORGIA EPD PLAN. F. THE COUNTY MAY DENY AN APPLICATION IF ADEQUATE WATER RESOURCES ARE NOT AVAILABLE OR IF THE PROPOSED USE IS DETERMINED TO ADVERSELY IMPACT EXISTING USERS SEC. 334 — GENERAL PROVISIONS (CONTINUED) (D) OPERATIONAL STANDARDS (4) POWER GENERATION A. PRIMARY ON-SITE GENERATION PROHIBITED UNLESS OTHERWISE AUTHORIZED THROUGH SPECIAL USE APPROVAL. SUCH APPROVAL SHALL REQUIRE A FINDING THAT THE PROPOSED GENERATION WILL NOT ADVERSELY IMPACT SURROUNDING PROPERTIES, AIR QUALITY, OR INFRASTRUCTURE. B. BACKUP GENERATORS SHALL ONLY BE PERMITTED FOR EMERGENCY USE. C. MUST COMPLY WITH ALL APPLICABLE EPA EMISSIONS STANDARDS. SEC. 335 - ENVIRONMENTAL AND EMERGENCY REQUIREMENTS A. COORDINATION WITH CAMDEN COUNTY FIRE RESCUE AND EMA SHALL BE REQUIRED B. AN ENVIRONMENTAL IMPACT ANALYSIS SHALL BE CONDUCTED C. A WATER WITHDRAWAL PERMIT APPLICATION SHALL BE SUBMITTED TO EPD (IF THRESHOLDS MET). SEC. 336 — PUBLIC HEARINGS IN ADDITION TO SEC. 1211 (PUBLIC NOTICE) A. ALL ADJACENT PROPERTY OWNERS WITHIN 1,500 FEET OF THE SUBJECT PROPERTY SHALL BE NOTIFIED VIA FIRST CLASS MAIL NO LESS THAN 15 DAYS PRIOR TO THE HEARING DATE. SEC. 337 — APPLICATION REQUIREMENTS IN ADDITION TO SEC. 1214 (CONDITIONAL APPROVAL OF ZONING CHANGES), THE FOLLOWING SHALL BE SUBMITTED: A. UTILITY LETTERS OF AVAILABILITY; B. ELECTRICAL INFRASTRUCTURE PLAN IDENTIFYING SUBSTATIONS, TRANSMISSION LINES, AND COORDINATION WITH THE SERVING ELECTRIC UTILITY, FACILITIES EXCEEDING 50 MW REQUIRE ENHANCED REVIEW; C. NOISE IMPACT ANALYSIS; D-/WATFER-USE -AND-CONSERVAHON PLAN; E. DETAILED WATER DEMAND ANALYSIS SHOWING DAILY, PEAK, AND ANNUAL WATER USE PROJECTIONS. F. COPY OF WATER WITHDRAWAL PERMIT APPLICATION SUBMITTED TO EPD (IF THRESHOLDS MET) AND A TIMELINE FOR PERMIT APPROVAL. G. WATER CONSERVATION PLAN DEMONSTRATING COMPLIANCE WITH STATE GROUNDWATER USE RULES AND ANY APPLICABLE COASTAL WATER CONSERVATION CONDITIONS. H. ENERGY USE AND SUSTAINABILITY PLAN; I. STORMWATER MANAGEMENT PLAN; J. ENVIRONMENTAL IMPACT ANALYSIS; K. DECOMMISSIONING AND SITE REUSE PLAN, PROVIDED FOR PLANNING AND INFORMATIONAL PURPOSES ONLY, IDENTIFYING POTENTIAL FUTURE REUSE SCENARIOS, ANTICIPATED INFRASTRUCTURE REMOVAL, AND SITE STABILIZATION MEASURES. SUBMISSION OF A DECOMMISSIONING AND SITE REUSE PLAN SHALL NOT, BY ITSELF, IMPOSE A FINANCIAL GUARANTEE OR ABANDONMENT OBLIGATION UNLESS EXPRESSLY REQUIRED AS A CONDITION OF A SPECIAL USE PERMIT, DEVELOPMENT AGREEMENT, OR OTHER LEGALLY AUTHORIZED APPROVAL. L. THE COUNTY MAY REQUIRE A DEVELOPMENT AGREEMENT FOR ANY DATA CENTER, PARTICULARLY HYPERSCALE FACILITIES, TO ADDRESS INFRASTRUCTURE, PUBLIC SERVICES, AND LONG-TERM OPERATIONAL CONDITIONS. SEC. 338 — ARCHITECTUAL AND DESIGN STANDARDS A. BUILDINGS VISIBLE FROM PUBLIC RIGHTS-OF-WAY SHALL INCORPORATE ARCHITECTURAL ARTICULATION, FENESTRATION, MURALS, OR GLAZING ON AT LEAST THIRTY (30) PERCENT OF THE FRONT FACADE. B. PROHIBITED EXTERIOR MATERIALS INCLUDE CORRUGATED METAL, VINYL SIDING, UNFINISHED CONCRETE BLOCK, AND SIMILAR LOW-DURABILITY MATERIALS. C. MECHANICAL AND ROOFTOP EQUIPMENT SHALL BE FULLY SCREENED FROM PUBLIC VIEW USING ARCHITECTURALLY INTEGRATED ELEMENTS. SEC. 339 — DECOMMISSIONING A. FACILITIES INACTIVE FOR 12 MONTHS SHALL BE CONSIDERED ABANDONED SEC. 340 - ENFORCEMENT AND SEVERABILITY A. ANY VIOLATION OF THIS ORDINANCE SHALL BE SUBJECT TO ENFORCEMENT AS PROVIDED IN THE CAMDEN COUNTY UNIFIED DEVELOPMENT CODE. B. IF ANY SECTION, SUBSECTION, SENTENCE, CLAUSE, OR PHRASE OF THIS ORDINANCE IS DECLARED INVALID OR UNCONSTITUTIONAL BY A COURT OF COMPETENT JURISDICTION, SUCH DECISION SHALL NOT AFFECT THE VALIDITY OF THE REMAINING PORTIONS, WHICH SHALL REMAIN IN FULL FORCE AND EFFECT. CONCLUSION BASED ON OUR REVIEW OF OTHER JURISDICTIONS, INCLUDING COWETA COUNTY, KINGSLAND, JONES COUNTY, MONROE COUNTY, AND COLLETON COUNTY, WE BELIEVE THIS ORDINANCE REFLECTS BEST PRACTICES FROM EACH. IT IS DESIGNED TO ENSURE THAT, IF DATA CENTERS COME TO CAMDEN COUNTY, THEY DO SO IN A MANNER THAT IS COMPATIBLE WITH THE COMMUNITY AND PROTECTIVE OF ENVIRONMENTALLY SENSITIVE AREAS. Adjournment: Chairman Cheek adjourned the April 21, 2026 Work Session at approximately 5:49 PM. The motion carried unanimously. BY: ______________ _____________________________________________ ROBBIE CHEEK, CHAIRMAN CAMDEN COUNTY BOARD OF COMMISSIONERS ATTEST: ______________________________________ KATIE BISHOP, COUNTY CLERK