City: Alpharetta
Alpharetta Planning Commission regular meeting, November 5, 2026
6:30 PM · 11 pages
These are the minutes as Alpharetta Planning Commission posted them, read from the file on its own website. Georgia Commons is independent and is not affiliated with Alpharetta Planning Commission.
Records of this meeting
Each link opens the body's own website or meeting portal.
- MinutesPlanning Commission Minutes 10-1-26 (alpharettaga.api.civicclerk.com) · shown on this page
- Video recordingPlanning Commission Meeting November 2026 (cpmedia.azureedge.net)
Summary
Written by an AI model (claude-sonnet-5-5) from the minutes below. It is not the record: the minutes are.
Planning commission unanimously approved a Georgia Power substation at a Royal 400 data center, a Windward restaurant, and vehicle parking code changes.
The commission took up three public hearing items and approved each by a 6-0 vote. It approved a master plan amendment, conditional use, and variance for a Georgia Power utility substation at the Royal 400 data center at 4905 North Point Parkway, with 30 conditions, including amended wording on conditions 6, 9 and 13 and a new condition requiring a public art sculpture at least 12 feet tall. It approved a master plan amendment, variance, and exception for a free-standing restaurant (no drive-thru) at 0 Windward Parkway, with staff's conditions. It also approved text amendments to the Unified Development Code (UDC) defining business and recreational vehicles and changing parking rules in residential districts. A rezoning and variances for 350 Wills Lane were deferred by the applicant and not considered. The minutes of September 3, 2026 were also approved.
Topics taken up: Royal 400 data center utility substation; Georgia Power substation screen walls; public art sculpture condition; Windward restaurant at 0 Windward Parkway; cantilevered outdoor seating variance; business and recreational vehicle parking rules; Unified Development Code amendments; 350 Wills Lane deferral.
Decisions the minutes record (3)
Each decision is followed by the sentence of the minutes that records it, copied word for word.
Master plan amendment, conditional use, and variance for Georgia Power utility substation at Royal 400 Data Center, 4905 North Point Parkway
6-0
The minutes: “Commissioner Richard offered a motion to approve subject to the Conditions as reviewed by Mr.”
Master plan amendment, variance, and exception for free-standing restaurant at 0 Windward Parkway, Windward Pod 14A
6-0
The minutes: “Commissioner Perkins offered a motion to approve with the conditions as noted by Staff.”
Unified Development Code text amendments on business and recreational vehicle definitions and residential parking
6-0
The minutes: “Vice-Chair Reynolds offered a motion to approve with the conditions as presented by Ms. Cook.”
Agenda items (5)
Found in the minutes by their headings. Where an outcome is shown, it was read by rule from the item's own words: a guide to the text, not part of the record.
- 2. ROLL CALL
- 3. APPROVAL OF MEETING MINUTES
- 6. PUBLIC HEARING
- 8. Building materials shall be medium neutral colors (no white) to diminish visibility from the street. Building roof top units shall not be visible from the…
- 15. Developer shall be responsible to implement the recommendations in the traffic study, as approved by Staff.
The minutes
As posted on alpharettaga.api.civicclerk.com, read November 19, 2026. Nothing below is written by Georgia Commons.
PLANNING COMMISSION MEETING
OFFICIAL Minutes
OCTOBER 1, 2026
ALPHARETTA CITY HALL
COUNCIL CHAMBERS
2 PARK PLAZA
6:30 PM This summary is provided as a convenience and service to the public, media, and staff. It is not the intent to record proceedings verbatim. Any reproduction of this summary must include this notice. This is not an official record of the Alpharetta Planning Commission Meeting proceedings. Meetings are recorded and available for review at https://www.youtube.com/user/alpharettagov
1. CALL TO ORDER
2. ROLL CALL
Commissioners Present:
1. Francis Kung’u, Chair
2. Jill Reynolds, Vice-Chair
3. Dennis Mitchell
4. William Perkins
5. Karen Richard
6. Todd Stratton
B. Staff Present:
1. Kathi Cook, Director of Community Development
2. Michael Woodman, Planning & Development Services Manager
3. Elle Taylor, Planning & Zoning Coordinator
4. Seth Holbrook, GIS /Special Projects Planner
3. APPROVAL OF MEETING MINUTES
a. Approve Meeting Minutes of 9-3-26.
❖ Vice-Chair Reynolds offered a motion to approve.
• Commissioner Richard seconded the motion.
• The motion carried (6-0)
4. ITEMS FROM BOARD MEMBERS
5. ITEMS FROM STAFF
6. PUBLIC HEARING
a. Public Hearing Procedure Elle Taylor read public hearing procedure.
b. Z-26-07/V-26-15 350 Wills Lane This item was deferred by the applicant. It was not considered on October 1, 2026. Consideration of a rezoning and variances to allow for the subdivision of a 4.98-acre property into 3 single-family detached lots. A rezoning is requested from AG (Agriculture) to R (Dwelling, ‘For-Sale’, Residential). Variances are requested to Unified Development Code (UDC) Subsection 2.2.3(D) to reduce the side setback from 25’ to
15’ and UDC Subsection 3.5.2 to modify the local street section to allow for no curb or sidewalks. The property is located at 350 Wills Lane and is legally described as being located in Land Lots 597, 598, and 599, 1st District, 2nd Section, Fulton County, Georgia.
c. MP-26-13/CU-26-11/V-26-19 Royal 400 Data Center Michael Woodman, Planning & Development Services Manager, presented consideration of a request for master plan amendment, conditional use, and variance to allow a Georgia Power utility substation in conjunction with an expansion at an existing data center on 38.8 acres in the Royal 400 Master Plan. A master plan amendment is requested to amend the Royal 400 Master Plan to add ‘Utility Substation’ as a conditional use, reduce an undisturbed buffer, amend security fence materials and height. A conditional use is requested to allow a ‘Utility Substation’ on the subject property and a variance is requested to Unified Development Code Subsection 2.3.6 to allow the height of a fence or wall to exceed eight feet (8’). The property is located at 4905 North Point Parkway and is legally described as being located in Land Lots 850, 851, 858 & 859, 1st District, 2nd Section, Fulton County, Georgia.
• Location Map.
• Current Zoning.
• Previous Master Plan Amendments.
• Surrounding properties.
• Photos of Site.
• Transmission line.
• Miscellaneous Regulations in the Code requiring a 40’ undisturbed buffer for a Data Center were written after approval of this site.
• Code also included specific fencing requirements.
• The master plan amendment and variance request seeks to reduce the undisturbed buffer along Kimball Bridge Road to 40’ where the ‘Utility Substation’ is proposed and to allow 22’ screen walls around the ‘Utility Substation’. According to the applicant, 22’ is the approximate height of the tallest equipment in the utility substation. In addition, a 22’ screen wall is proposed off-site along the street frontage of the Georgia Power utility substation property located directly across Kimball Bridge Road from the applicant’s property.
• Applicant has also agreed to install a 22’ screen wall along the street frontage of the Georgia Power property across Kimball Bridge Rd. from this site.
• The Unified Development Code (UDC) allows a ‘Utility Substation’ as a permitted use in the SU (Special Use) zoning district and as a conditional use in all other zoning districts, except the MU (Mixed Use) district. A land disturbance permit (LDP) was issued for the proposed data center expansion in August 2024, with site work beginning immediately after.
• As a result, the applicant ceased constructed activities pending the outcome of the current public hearing request to allow the on-site ‘Utility Substation’.
• Staff encouraged the applicant to explore an alternate, less-visible location for the utility substation that minimizes impacts to the undisturbed buffer, as well as alternative energy sources.
• Existing Site with Utility Station.
• Applicant provided an alternate site plan depicting the utility substation on the south side of the existing building and having minimal impacts to the 100’ buffer along North Point Parkway. However, Georgia Power requires a 300’ wide right-of-way for overhead lines and maintenance clearances (denoted in the red cross-hatching) connecting the utility substation to the existing 100’ Georgia Power easement, which would impact hundreds of trees on the North Point Parkway side of the building.
• Issues with providing alternative energy source.
• Existing Buffer – little vegetation existing today.
• Tree Survey and Assessment.
• Stormwater Facilities on the property.
• Updated Screen Wall Exhibit.
• Existing Site with no screening and after screen wall as well as 10 years of growth.
• Safe Fence product proposed by the Applicant is a non-conductive material.
• Review Criteria for Master Plan Amendment, Conditional Use and Variance:
▪ The proposed data center expansion was previously approved in 2008 and there are other data centers operating in the Royal 400 Master Plan.
▪ The proposed data center expansion was permitted and under construction at the time that Georgia Power required the applicant to construct an on-site utility substation to serve the subject property and free up available capacity at the off-site Georgia Power substation currently serving the property. In addition, the on-site utility substation places the financial burden of electrical grid upgrades with the data center and not with the energy provider or its customers.
▪ The property has exceptional conditions related to its size, shape, and topography. The proposed screen walls on the subject property are setback at a minimum 40’ from Kimball Bridge Road, with nearly two-thirds (2/3) of the wall setback at least 100’ from Kimball Bridge Road. In addition, there is existing vegetation between the proposed screen wall and Kimball Bridge Road, which will help the wall blend in with the surroundings sooner. If approved, landscape screening material is recommended in lieu of a screen wall along the frontage of the Georgia
Power property.
• CZIM.
• Citizen Participation Plan.
Staff has reviewed the applicant’s proposal against the review criteria for a master plan amendment, conditional use, and variance. The proposal would permit a suitable use in view of the use and development of adjacent and nearby properties.
The proposed data center expansion was previously approved in 2008 and there are other data centers operating in the Royal 400 Master Plan. Screen walls and landscape screening are proposed to screen the utility substation on the subject property, as well as the substation on the Georgia Power property directly across from the subject property. In addition, the applicant has demonstrated that alternate locations for the utility substation would result in significant tree impacts. The proposed data center expansion was permitted and under construction at the time that Georgia Power required the applicant to construct an on-site utility substation to serve the subject property and free up available capacity at the off-site Georgia
Power substation currently serving the property. In addition, the on-site utility substation places the financial burden of electrical grid upgrades with the data center and not with the energy provider or its customers. Since the utility substation would
occupy a similar land area as the future office building, it is recommended that the property be limited to the existing data center and expansion only.
Staff’s recommendation is to approve MP-26-13/CU-26-11/V-26-19 Royal 400 Data Center, subject to the following conditions (Conditions 1-24 below are related to file #MP-08-09/V-08-15 Royal 400/Data Center with changes reflected in RED):
1. The property shall be limited to the existing data center and the proposed Data Center expansion which shall not exceed 245,200 sq. ft. The applicant shall locate buildings, entrance and parking area where the least impact to trees is present, with final approval by Staff.
2. The property owner shall be required to build up to 394 additional parking spaces in the future if the City determines and can document that a parking shortage exists.
3. Land for additional parking shall be set aside and preserved as green space until such time as additional parking is needed. This land shall not be subdivided from the remainder of the property so that it can be used for parking in the future. This parking reserve land shall be in addition to required tree save areas.
4. The future office building shall be located closer to the corner of Kimball Bridge Road and North Point Parkway than structured or surface parking. Parking shall be located interior to the site and shall not be situated on the corner of Kimball Bridge Road and North Point Parkway.
5. In order to provide heavy natural screening at the corner of Kimball Bridge and North Point Parkway, stormwater facility #1 shall be relocated.
6. Except for one driveway access and sign on North Point Parkway, and where the utility substation encroaches up to 60’ into the undisturbed buffer on the site plan prepared by Lowe Engineers, revised 9/16/26, the first 100 ft. of property along the entire length of Kimball Bridge Road and North Point Parkway (from future right-of-way lines) shall be designated as an undisturbed buffer. The buffer shall be heavily replanted to include predominately evergreens where sparse in order to obscure buildings and parking from street views. The buffer shall be left undisturbed following construction of project improvements and installation of required enhancements. Areas of the undisturbed buffer between Kimball Bridge Road and the screen walls surrounding the utility substation shall be heavily replanted to City buffer standards where sparse in order to obscure the utility substation and building from street views.
7. No access or signage shall be located along Kimball Bridge Road. One driveway access and sign shall be permitted on North Point Parkway. Access and signage shall also be permitted on Great Oaks Way.
8. Building materials shall be medium neutral colors (no white) to diminish visibility from the street. Building roof top units shall not be visible from the roadways. Site design shall be approved by Staff. Building elevations shall incorporate the use of brick and be approved by the Design Review Board.
9. All loading areas and cooling equipment shall be screened with a wall built with the same materials as the building as well as landscape screening. In addition to obscuring the view, the screening wall around the cooling equipment shall be designed to prevent the transmission of either high-pitched or low-level sounds generated by any equipment at this location from extending beyond the property limits.
10. Site shall not be mass graded and clearing shall be limited to each phase of construction.
11. Prior to Land Disturbance Permit process, applicant shall provide an accurate survey of trees near proposed disturbed edges.
12. Construction slopes shall be planted with a mixture of native species 8’ in height, 10’ on center and approved by Staff.
13. Security fence shall be decorative metal black fence screened with landscaping from the public right of way and limited to 8’ in height, except that screen walls used to screen the utility substation on the subject property shall be substantially as depicted in the amended application materials and limited to 22’ in height, with final approval by DRB. In lieu of the screen wall on the Georgia Power property, developer shall plant a 20’ wide landscape buffer to City buffer standards for the length of the existing utility substation along Kimball Bridge Road, with final approval by DRB.
14. The number of parking spaces required on the property is subject to reevaluation if the use changes or projected number of employees grows greater than 20.
15. Intersection Design — All proposed curb cuts must also comply with AASHTO Design Guidelines; in particular, adequate Intersection Sight Distance must be provided and demonstrated by the engineer-of-record.
16. If sight distance is unable to be met on the proposed North Point Parkway curb cut. This curb cut will be restricted to movements able to meet sight distance requirement. These restricted movement designs will need to be approved by the Engineering Department.
17. Access to the signalized intersection at Great Oaks Way and North Point Parkway should be provided to allow safe access to northbound North Point Parkway.
18. Provide Traffic Study for proposed development. Meet with Traffic Engineering Department to determine scope.
19. Provide right-of-way required for North Point Parkway and Kimball Bridge Road intersection improvements.
20. Future floodplain study is required on intermittent stream area if drainage basin is 100 acre or greater.
21. Army Corps permitting may be required with final development plans and stream determination.
22. Initial Phase 1 pond should be sized per the Unified Development Code, have 3:1 slopes, and be located to save specimen trees.
23. Parking deck shall be a maximum of 3 levels above grade. Where visible, deck shall be faced with similar material as primary building.
24. Royal 400 original Master Plan conditions shall apply except were conflicts exist with these conditions.
25. ‘Utility Substation’ shall be added as a conditional use in the Royal 400 Master Plan.
26. ‘Utility Substation’ shall be added as a conditional use at 4905 North Point Parkway and limited to the location and size depicted on the site plan prepared by Lowe Engineers, revised 9/16/26.
27. ‘Utility Substation’ shall only serve the subject property and there shall not be additional connections made to the utility substation.
28. Developer shall perform a noise study on the utility substation to verify compliance with the City’s noise ordinance, which shall be submitted prior to the issuance of a Certificate of Occupancy for the data center expansion.
29. Trees shall be saved as depicted on the site plan prepared by Lowe Engineers, revised 9/16/26.
There was discussion from the Commission:
• Condition #6 (adding as approved by Staff.)
• Public Notification process.
• Reason for installation of Landscape material across the street being provided by Applicant.
• Condition #27 -Payment for Substation.
• Requirement of Utility Substation by Georgia Power.
• Original LDP in 2024 did not consider a utility substation.
• Condition #13( adding date for amended application materials.)
• Screen wall color and materials.
• Condition # 9.( adding “power and cooling materials” and “As approved by Staff”
• Condition # 2. Requirement that property owner shall build up to 394 additional parking spaces in the future if need is determined by the City. This is in case of future conversion to office. There is no additional parking being contemplated today.
• Possibility of additional transmission lines.
Applicant gave a presentation.
• History of Site.
• Location to avoid further movement of trees.
• Transmission lines.
• Screening of the substation.
• Will work with the City to determine a design.
• Sample of proposed screening material.
• Intent is to camouflage with screening wall and plantings.
• Agreed to proposed change to Condition #9 with the flexibility to be approved by Staff. Intent is to aesthetically blend with the building.
There was discussion from the Commission:
• This is not an AI Data Center. It is substantially smaller.
• Serves Financial Services clients.
• No additional clients will be added.
• Closed Loop water consumption.
• Owner will pay for power usage.
• Safety.
• Noise – Applicant willing to provide an acoustic study.
• Screen Wall/Vegetation – mitigation for noise.
• Magnetic Field.
• Proposed Substation is similar to those that have been in existence for a long time.
• Power and water usage system uses less water than a small number of residential homes.
• Alternate Locations.
• Easement for Substation.
• “In & Out Line requires 4 lines with distance requirements.
• Transmission Lines.
• Right of Way.
• Existing trees.
• Possible Sculpture at corner of Kimball Bridge and North Point.
There was no public comment.
There was discussion from the Commission:
• Possible Condition # 30 - “Developer shall provide a public art sculpture at the corner of and this would
be Kimball Bridge Road and North Point Parkway with a minimum of 12’subject to approval by the Cultural Arts Commission.”
❖ Commissioner Richard offered a motion to approve subject to the Conditions as reviewed by Mr.
Woodman with the following changes, On Condition # 6 add the last sentence there “ As approved by Staff.
Condition #9 “ All loading areas and power and cooling equipment shall be screened with a wall built with the same materials as the building, as well as landscape screening as approved by Staff. In addition to obscuring the view, the screening wall around the power and cooling equipment shall be designed to prevent the transmission of either high-pitched or low-level sounds generated by any equipment at this location from extending beyond the property limits.
Condition #13 We agreed to add the date for the recently submitted screen wall.in the first sentence “ Except that the screen walls used to screen the utility substation on the subject property shall be substantially depicted in the amended application materials dated 9-25-26 and the rest of the condition continues with no changes.
Add Condition #30 “ Developer shall provide a public art sculpture at the corner of Kimball Bridge and North Point Parkway with a minimum height of 12’ subject to approval of the Cultural Arts Commission.
• Vice- Chair Reynolds seconded the motion.
• The motion carried (6-0) Final Conditions:
1. The property shall be limited to the existing data center and the proposed Data Center expansion which shall not exceed 245,200 sq. ft. The applicant shall locate buildings, entrance and parking area where the least impact to trees is present, with final approval by Staff.
2. The property owner shall be required to build up to 394 additional parking spaces in the future if the City determines and can document that a parking shortage exists.
3. Land for additional parking shall be set aside and preserved as green space until such time as additional parking is needed. This land shall not be subdivided from the remainder of the property so that it can be used for parking in the future. This parking reserve land shall be in addition to required tree save areas.
4. The future office building shall be located closer to the corner of Kimball Bridge Road and North Point Parkway than structured or surface parking. Parking shall be located interior to the site and shall not be situated on the corner of Kimball Bridge Road and North Point Parkway.
5. In order to provide heavy natural screening at the corner of Kimball Bridge and North Point Parkway, stormwater facility #1 shall be relocated.
6. Except for one driveway access and sign on North Point Parkway, and where the utility substation encroaches up to 60’ into the undisturbed buffer on the site plan prepared by Lowe Engineers, revised 9/16/26, the first 100 ft. of property along the entire length of Kimball Bridge Road and North Point Parkway (from future right-of-way lines) shall be designated as an undisturbed buffer. The buffer shall be heavily replanted to include predominately evergreens where sparse in order to obscure buildings and parking from street views. The buffer shall be left undisturbed following construction of project improvements and installation of required enhancements. Areas of the undisturbed buffer between Kimball Bridge Road and the screen walls surrounding the utility substation shall be heavily replanted to City buffer standards where sparse in order to obscure the utility substation and building from street views, as approved by Staff.
7. No access or signage shall be located along Kimball Bridge Road. One driveway access and sign shall be permitted on North Point Parkway. Access and signage shall also be permitted on Great Oaks Way.
8. Building materials shall be medium neutral colors (no white) to diminish visibility from the street. Building roof top units shall not be visible from the roadways. Site design shall be approved by Staff. Building elevations shall incorporate the use of brick and be approved by the Design Review Board.
9. All loading areas and power and cooling equipment shall be screened with a wall built with the same materials as the building as well as landscape screening, as approved by Staff. In addition to obscuring the view, the screening wall around the power and cooling equipment shall be designed to prevent the transmission of either high-pitched or low-level sounds generated by any equipment at this location from extending beyond the property limits.
10. Site shall not be mass graded and clearing shall be limited to each phase of construction.
11. Prior to Land Disturbance Permit process, applicant shall provide an accurate survey of trees near proposed disturbed edges.
12. Construction slopes shall be planted with a mixture of native species 8’ in height, 10’ on center and approved by Staff.
13. Security fence shall be decorative metal black fence screened with landscaping from the public right of way and limited to 8’ in height, except that screen walls used to screen the utility substation on the subject property shall be substantially as depicted in the amended application materials, dated 9/25/26, and limited to 22’ in height, with final approval by DRB. In lieu of the screen wall on the Georgia Power property, developer shall plant a 20’ wide landscape buffer to City buffer standards for the length of the existing utility substation along Kimball Bridge Road, with final approval by DRB.
14. The number of parking spaces required on the property is subject to reevaluation if the use changes or projected number of employees grows greater than 20.
15. Intersection Design — All proposed curb cuts must also comply with AASHTO Design Guidelines; in particular, adequate Intersection Sight Distance must be provided and demonstrated by the engineer-of-record.
16. If sight distance is unable to be met on the proposed North Point Parkway curb cut. This curb cut will be restricted to movements able to meet sight distance requirement. These restricted movement designs will need to be approved by the Engineering Department.
17. Access to the signalized intersection at Great Oaks Way and North Point Parkway should be provided to allow safe access to northbound North Point Parkway.
18. Provide Traffic Study for proposed development. Meet with Traffic Engineering Department to determine scope.
19. Provide right-of-way required for North Point Parkway and Kimball Bridge Road intersection improvements.
20. Future floodplain study is required on intermittent stream area if drainage basin is 100 acre or greater.
21. Army Corps permitting may be required with final development plans and stream determination.
22. Initial Phase 1 pond should be sized per the Unified Development Code, have 3:1 slopes, and be located to save specimen trees.
23. Parking deck shall be a maximum of 3 levels above grade. Where visible, deck shall be faced with similar material as primary building.
24. Royal 400 original Master Plan conditions shall apply except were conflicts exist with these conditions.
25. ‘Utility Substation’ shall be added as a conditional use in the Royal 400 Master Plan.
26. ‘Utility Substation’ shall be added as a conditional use at 4905 North Point Parkway and limited to the location and size depicted on the site plan prepared by Lowe Engineers, revised 9/16/26.
27. ‘Utility Substation’ shall only serve the subject property and there shall not be additional connections made to the utility substation.
28. Developer shall perform a noise study on the utility substation to verify compliance with the City’s noise ordinance, which shall be submitted prior to the issuance of a Certificate of Occupancy for the data center expansion.
29. Trees shall be saved as depicted on the site plan prepared by Lowe Engineers, revised 9/16/26.
30. Developer shall provide a public art sculpture at the corner of Kimball Bridge Road and North Point Parkway with a minimum height of 12’, subject to approval by the Cultural Arts Commission.
d. MP-26-08/V-26-08/E-26-05 Windward Hall/Windward MP Pod 14A Michael Woodman, Planning & Development Services Manager, presented consideration of a master plan amendment, variance, and exception to allow a free-standing ‘Restaurant (no drive-thru)’ on 3.75 acres in Windward. A master plan amendment is requested to the Windward Master Plan Pod 14A to allow a free-standing ‘Restaurant (no drive-thru)’ as a principal use on the property. A variance is requested to Unified Development Code (UDC) Subsection 3.3.2(D) to allow an outdoor seating area to encroach into the impervious setback of a stream and an exception is requested to UDC Section 2.5 to eliminate parking requirements for an outdoor seating area. The property is located at 0 Windward Parkway and is legally described as being located in Land Lot 1113, 2nd District, 1st Section, Fulton County, Georgia.
Georgia Power requested that the applicant construct an on-site Georgia Power electrical substation to serve the subject property and free up available capacity at the off-site Georgia Power substation currently serving the property.
• Current Zoning CUP.
• Windward Master Plan Amendments.
• Windward POD 14A designation as Business Center.
• Windward LCI plan:
▪ Envisions the subject property as a connected experiential retail opportunity by pairing food and beverage with a focus on the natural environment and programming and events to attract surrounding office employees located within a walkable distance. Less auto-dependent retail models are more stable in the market and increasingly serve local markets. Several of Alpharetta’s top employers are located within one-half (1/2) mile of the subject property, including Morgan Stanley, Global Payments, ADP, Lexis Nexis, and AT&T representing an estimated 11,000 employees. According to CoStar, there are seventeen (17) office buildings totaling approximately 1.9 million square feet within one-half (1/2) mile of the property.
The occupancy rate of those office buildings is 94.6%.
▪ Envisions amenitizing the area’s office parks with a system of multi-use trails in an area known for high automobile dependence with 99% of workers commuting via car.
• An extension of Dryden Road is recommended between North Point Parkway and Edison Drive.
The extension provides an alternative to using Windward Parkway and connects to the MARTA Park-and-Ride. A mainline trail is depicted traversing the subject property along the north side of the stream. The trail is intended to provide an alternative connection to the MARTA Park-and-Ride by providing a more enjoyable and efficient means of travel. The trail also connects to the Big Creek Connector and Camp Creek Circulator. The Big Creek Connector is a two (2) mile loop, which follows the Big Creek Greenway, an existing power easement, and Caney Creek and the Camp Creek Circulator is a one (1) mile loop along Camp Creek near Lexis Nexis and Windward Plaza.
• Site Plan :
• Free standing restaurant adjacent to the stream buffers at the south end of the property.
• Parking is located behind the building and on adjacent streets.
• Outdoor seating area is situated behind the building and is cantilevered over the natural stream buffer area.
• Tree save area.
• Retaining wall along the edge of the parking lot adjacent to Edison drive.
• Stormwater management.
• Renderings.
• Traffic.
• Standards for Master Plan Amendments.
• The Windward LCI envisions the property as a connected, experiential retail opportunity combining food and beverage with the natural environment and programming and events to attract and support surrounding office employees located within a walkable distance. The applicant’s proposal is consistent with the vision and recommendations in the LCI and would serve as an amenity for office workers in adjacent and nearby properties.
• Exception Criteria:
▪ The property has exceptional conditions due to its shape and topography. However, Staff encouraged the applicant to seek an exception in order to implement the vision for the
property in the Windward LCI. The cantilevered outdoor seating area would help activate the natural area along the stream, which will include a future multi-use trail alignment.
• Citizen participation Plan
• Community Zoning Information Meeting.
Staff reviewed the applicant’s proposal against the established review criteria for a master plan amendment, variance, and exception. The proposal is consistent with the Windward LCI, which envisions the property as a connected, experiential retail opportunity combining food and beverage with the natural environment and programming and events to attract and support surrounding office employees located within a walkable distance. The proposed free-standing restaurant will blend dining offerings with nature and a future multi-use trail alignment to attract and support surrounding office employees. The proposal is consistent with the LCI vision and recommendations and would serve as an amenity for the area’s office employees. The proposal would encourage pedestrian trips and reduce vehicular trips.
The property has exceptional and peculiar conditions related to its shape and topography, multiple road frontages, presence of
a perennial stream, as well as having a new vision for the property. Staff encouraged the cantilevered outdoor seating area in order to activate and interact with the natural area and future multi-use trail alignment along the stream, which is consistent with the vision for the property in the Windward LCI. If approved, it is recommended that the applicant dedicate an easement or land for a multi-use trail along the stream.
Staff’s recommendation is to approve MP-26-08/V-26-08/E-26-05 Windward Hall/Windward MP Pod 14A, subject to the following conditions:
1. The site shall be developed substantially similar to the site plan prepared by Paradigm, dated 9/1/26, except for modifications necessary to comply with these conditions.
2. Building architecture and exterior materials shall comply with the DRB Design Guidelines and be compatible with the existing buildings in the area, subject to final approval by DRB. Exterior materials shall be primarily brick or stone and the building shall have 4-sided architecture, details, and materials, as approved by DRB. Developer shall revise the rendering/elevation to comply with the following, subject to final approval by DRB:
a. Glass shall have a transparency (visible light transmission) higher than 70% and must have an external reflectance of less than 15%;
b. Building shall have a clear base, middle, and top, with stone or masonry at the base and a defined cap at the roofline;
c. Horizontal proportions of the entry shall be strengthened so that the base and columns do not appear too tall and narrow. Columns shall have a base. Recommend studying 4 canopy columns instead of 6 to create a more open, prominent arrival;
d. Increase the visual thickness of the arrival canopy so it has enough weight for the scale of the building; and
e. Add well-placed horizontal divisions to the tall arched windows so they relate better to the rest of the façade.
3. ‘Restaurant, no drive-through’ shall be added as a permitted principal use in Pod 14A of the Windward Master Plan.
4. Developer shall improve the Windward Parkway streetscape as follows: minimum 6’ planter (planted with street trees and grasses), minimum 10’ concrete sidewalk, and decorative pedestrian lighting, with final approval by Staff.
5. Developer shall improve the Edison Drive streetscape as follows: minimum 6’ planter (planted with street trees and grasses), minimum 6’ concrete sidewalk, and decorative pedestrian lighting, with final approval by Staff.
6. Landscape strips along Edison Drive and Windward Parkway shall be planted with a mix of trees, shrubs and grasses, as approved by DRB.
7. Retaining walls visible from the street shall be faced with brick or stone, as approved by DRB. Retaining walls over 16’ in height shall be terraced with a minimum 5’ landscape area between terraces. Trees, shrubs, and vines shall be planted along the base of the wall to soften the appearance, with final approval by DRB.
8. Outdoor seating area, as depicted on the site plan prepared by Paradigm, dated 9/1/26, shall be constructed prior to the issuance of a Certificate of Occupancy for the restaurant, as approved by Staff.
9. Outdoor seating area encroachment into the impervious setback and stream buffer shall be limited to the encroachment as depicted on the site plan prepared by Paradigm, dated 9/1/26.
10. Developer shall replant to City buffer standards the areas of the impervious setback depicted to be graded, with final approval by Staff.
11. Developer shall dedicate land or an easement allowing for public access over a future multi-use trail alignment running through the impervious setback and/or City stream buffer, with final alignment as approved by Staff.
12. Developer shall save trees as depicted on the site plan prepared by Paradigm, dated 9/1/26. In addition, developer shall make reasonable efforts to save additional specimen, trees of quality and/or tree groupings, as approved by Staff.
13. Developer shall provide a public art sculpture at the corner of Windward Parkway and Edison Drive with a minimum height of 12’, subject to approval by the Cultural Arts Commission.
14. Developer shall improve a dedicated left turn lane on Edison Drive at the site driveway. The minimum length of the left turn lane shall be 185’ (135’ storage and 50’ taper), as approved by Staff. A modified RCUT median shall be provided along Edison Drive at the site driveway, with final approval by Staff.
15. Developer shall be responsible to implement the recommendations in the traffic study, as approved by Staff.
There was discussion from the Commission:
• Trail Connection.
• One restaurant.
• Site Plan.
• No tree saves proposed on Edison Dr.
• Renderings.
The Applicant gave a presentation.
• Background.
• Passion to become a chef.
• Buffet type meals to serve office community.
• Variety at Breakfast, lunch, dinner.
• Windward LCI.
• Renderings.
• Cantilevered outdoor seating.
• Variance request.
• Traffic.
• Tree Save area.
• Intent along Edison Drive is to have landscape planters, landscaping and sculpture.
There was discussion from the Commission:
• Cantilevered outdoor seating.
• Liked restaurant use for walkability, catering to office workers.
• Alcohol license.
• Size of Restaurant.
• Event space.
• Easement for multi-use trail..
There was no public comment.
❖ Commissioner Perkins offered a motion to approve with the conditions as noted by Staff.
• Commissioner Stratton seconded the motion.
• The motion carried (6-0)
e. PH-26-04 Unified Development Code – Amendments Business & Recreational Vehicles Kathi Cook, Director of Community Development, presented consideration of text amendments to Unified Development Code (UDC) Subsection 1.4 and UDC Subsection 2.5.4(B) to assign definitions and amend the locational parking requirements for business and recreational vehicles in residential zoning districts.
Staff recommends text amendments to Unified Development Code (UDC) Section 1.4 Definitions, to assign definitions for ‘Business Vehicle’ and ‘Recreational Vehicle’, and to UDC Subsection 2.5.4(B) Location of Required Parking in Residential Districts, to amend the locational parking requirements for business and recreational vehicles in residential zoning districts. The proposed text amendments are related to recent code enforcement cases involving the parking of a vehicle with a towing capacity greater than one-and-one-half (1 ½) tons on a residential property. In one case, the judge ruled against the City due to the lack of a definition for a business or recreational vehicle. In another case, a homeowner sought an administrative appeal from the Board of Zoning Appeals (BZA) because a variance to the recreational vehicle parking regulation was not permitted due to the use being prohibited.
• It is recommended that UDC Subsection 2.5.4 Locational Criteria for Parking be amended to clarify that the associated regulations exclude residential parking lots and structured parking decks, which are typically associated with ‘For-Rent’ residential development. Residential parking lots require landscape screening from the street and vehicles are typically not visible in structured parking decks. An amendment is proposed allowing one (1) business vehicle to be parked on a paved driveway, whereas the regulations currently require a business vehicle to be parked in an area not visible from the street. Recreational vehicle parking or storage would remain unchanged and limited to an area not visible from a street. Amendments are proposed which would
exclude AG-zoned residential properties from regulations pertaining to business and recreational vehicles with a carrying capacity of more than one-and-one-half (1 ½) tons and change the use from ‘prohibited’ to ‘not permitted’ to allow for City Council consideration of a hardship variance. A list of factors to be considered by City Council are recommended, including support from neighbors, exceptional conditions, economic hardship, and a determination that the variance would not cause a substantial detriment to the public good.
• Proposed amendments are related to recent code enforcement actions involving the parking of a vehicle with a towing capacity greater than one and a half tons on a residential property as well as homeowners that would like to request a variance from the code requirements.
• Since the code currently lists it as prohibited to park recreational vehicles and other vehicles in residential districts, even with neighborhood support, it may not be considered for a variance.
• Proposed changes to Ordinance.
There was discussion from the Commission:
• HOA Covenants take precedence over the code.
• Like that this adds clarity and provides a process.
❖ Vice-Chair Reynolds offered a motion to approve with the conditions as presented by Ms. Cook.
• Commissioner Perkins seconded the motion.
• The motion carried (6-0)
7. ADJOURNMENT
Chair Kung’u adjourned the meeting at 8:30 p.m.