111.03.08. Site requirements.

About this text

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

A. Flooding.

1) Lift stations shall remain fully operational and accessible during the 25-year flood.

2) All electrical controls shall be above the 100-year flood level.

3) All motors and mechanical equipment shall be protected against physical damage from the 100-year flood.

B. Access road.

1) Access roads to any lift station shall be paved.

2) Roads shall have a minimum of eight inches of graded aggregate base topped with a minimum of tow inches of asphalt Type "B" or six inches of reinforced concrete with control joints every ten feet.

3) Roads shall be a minimum of 12 feet wide.

4) A paved area inside the fencing shall be provided to facilitate service vehicle access to the pumping station wet well and other facilities.

5) A paved turn around area shall be provided at each pumping station.

6) All paved areas shall be contiguous with the paved access driveway.

C. Ownership.

1) Both the lift station site and the access road right-of-way shall have ownership dedicated to the city, and this shall be indicated on the subdivision plat.

2) The dedicated space for the lift station shall include sufficient space for parking of two trucks, plus turn-around, plus slope maintenance.

3) The dedicated width on road right-of-way shall be 30 feet minimum.

D. Fencing.

1) Lift station sites shall be fenced with a minimum of six-foot high chain link fencing topped with three strands of barbed wire.

2) Access gates shall be a minimum of 15 feet in width.

E. Water supply.

1) A metered water supply line (three-quarter-inch minimum size) shall be installed to the site, and a freeze-proof yard hydrant located near the wet well.

2) The hydrant shall be equipped with a suitable backflow preventer (Watts No. NF8 or approved equal).

F. Lighting.

1) All lift stations shall be provided with security lighting.

2) Security light must be mounted on a hinged pole with winch. Standard pole shall be a galvanized steel hinged square pole, General Electric No. ASHS-(XX)-2T-4.011 GV, 16 to 20 feet in height, with a General Electric No. M180 Winch/Chain and a No. RBSU2H6 GV Bracket. The security light attached to the top of the pole shall be a General Electric No. M2RR-07-S-1-H-2-LN-PEC1TL (Typ. for 2 lights) or alternate acceptable to the city.

G. Screening. Where natural screening is not present to screen the site from view of residences, special plantings shall be installed to screen the site.

H. Ground covers. All ground areas inside the fence and extending four feet beyond the fence shall be treated with a herbicide and covered with a geotextile fabric, followed with a four-inch thick layer of #57 stone.

The geotextile fabric shall be a non-woven polypropylene weighing eight oz./S.Y. with a minimum burst strength of 250 psi, such as Amoco Type 4553 or equal.

History

The history line the source prints at the end of the section.

(Ord. No. 2014-18, § 2, 8-21-2014)