111.03.09. Force mains.
About this text
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
A. The force main shall be sized for a minimum velocity of two and one-half feet per second with one pump operating.
B. Force mains of four-inch diameter or larger shall be ductile iron pipe. Smaller force mains may be used only with grinder pumps and shall be PVC pipe, SDR-21 with gasket joints. PVC pipe shall not be exposed to sunlight or freezing temperatures. Buried PVC pipe shall be marked continuously with metallized locator tape.
C. The force main profile shall slope continuously upward where practical. If high points occur where air could be trapped in the pipe, then an air release valve (of the type made for sewage applications) will be installed (in a manhole) at the high points.