Sec. 109-332. Fire hydrants.
About this text
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Fire hydrants shall be located and set in accordance with city specifications. Fire hydrants shall be required for all nonresidential land developments and all subdivisions. Fire hydrants with appropriate water pressure at appropriate intervals throughout the subdivision or land development shall be provided by the subdivider or land developer as required by the county fire department. Fire hydrants shall be located no more than 1,000 feet apart and within 500 feet of any principal dwelling. Hydrants, fittings, valves, and fire department connections shall be approved by the
county fire department. Fire department connections shall be not less than 18 inches or more than 36 inches above the level of the adjoining ground
or paving. The thread of such connections shall be uniform with that used by the county fire department. To eliminate future street openings, all underground utilities for fire hydrants, together
with the fire hydrants themselves, and all other supply improvements shall be installed before any final paving of a street within the right-ofway shared by such underground utilities.
History
(Ord. of 2-18-2003, § 804)
Read this code where it is posted (Municode) The source is the city's code as its publisher or its own website posts it. Check it there for later changes.