Flowery Branch · Zoning Ordinance

Appendix C - ZONING ORDINANCE / Article 32 - FLOODPLAIN MANAGEMENT

Sec. 32.45. Substantial Improvements of Nonresidential Structures in AO Zones.

About this text

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) Floodproofing Permitted. Substantial improvement of a non-residential structure may be floodproofed in lieu of elevation.

(b) Standards. The structure, together with attendant utility and sanitary facilities, must be designed to be water tight to the specified FIRM flood level plus

one (1) foot above the highest adjacent grade, with walls substantially impermeable to the passage of water, and structural components having the capability of resisting hydrostatic and hydrodynamic loads and the effect of buoyancy.

(c) Certification. A registered professional engineer or architect shall certify that the design and methods of construction are in accordance with accepted standards of practice.

(d) Drainage. Drainage paths shall be provided to guide floodwater around and away from any proposed structure.

History

The history line the source prints at the end of the section.

(Ord. No. 578, § 1, 8-1-2019)