9.5.2. Fire Hydrants and Valves

About this text

  • As published by Municode, current through 2026-05-28
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Fire hydrants are required for all subdivisions with water systems. Fire hydrants within residential developments must be located no more than 450 feet apart and at least six feet behind the curb or ditch line. To eliminate future street openings, all underground utilities for fire hydrants, together with the fire hydrants themselves and all other water supply improvements, must be installed before any base course application of a street shown on the subdivision

plat. All fire hydrants must be set plumb with outlets 18 inches above finished grade or 12 inches above a finished concrete surface. No valves may be located within the pavement or curb area.