Harlem · Zoning Ordinance
Part III - LAND DEVELOPMENT CODE / Chapter 102 - BUILDING REGULATIONS / Article VI - EXTERIOR LIGHTING IN THE MILITARY LIGHTING OVERLAY DISTRICT
Sec. 102-103. Maximum lighting levels.
About this text
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
The maximum lighting levels shall be within the ranges shown in Table 2, Lighting Levels, in foot candles.
Table 2—Lighting Levels Location or Type of Lighting Minimum Average Maximum
1. Parking Lots 0.6 2.4 10.0
2. Outdoor Display of Merchandise 0.5 5.0 15.0
3. Landscape and Decorative Areas 0.0 0.5 5.0
4. Walkways and Driveways 0.5 2.5 5.0
5. Canopies (Vehicular and Pedestrian) 5.0 10.0 15.0
(1) Areas under canopies. Areas under canopies (vehicular or pedestrian) shall have a maximum illuminance of 15 foot candles. Lighting under canopies shall be designed so as to not create glare beyond the outside edge of the canopy. Acceptable methods designed to prevent glare include the following:
a. The use of recessed fixtures incorporating lens covers that are recessed or flush with the bottom surface (ceiling) of the canopy; or
b. The use of the canopy edge as a shield.
History
(Ord. No. 2310, 8-28-2023)