Harlem · Zoning Ordinance
Part III - LAND DEVELOPMENT CODE / Chapter 102 - BUILDING REGULATIONS / Article VI - EXTERIOR LIGHTING IN THE MILITARY LIGHTING OVERLAY DISTRICT
Sec. 102-102. Fixture design standards.
About this text
- As published by Municode, retrieved 2026-11-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Unless modified by other provisions of this article or exempted under this article, all lighting shall comply with the following design standards:
(1) All exterior lighting fixtures on properties within the Military Lighting Overlay District in the City of Harlem with bulbs producing more than 1,000 lumens must be full cut-off or shielded and directed downward.
(2) All lighting shall have a maximum correlated color temperature (CCT) of 4000 Kelvin (K).
(3) All light coming from anywhere on the property may not exceed one-half foot candle of intensity at the property line of abutting residentially zoned property.
(4) Wall pack fixtures shall be full cut-off.
(5) Unshielded sag-lens, drop lens, or mercury vapor fixtures are prohibited.
History
(Ord. No. 2310, 8-28-2023)