McDuffie County · Zoning Ordinance
Part II - CODE OF ORDINANCES / Chapter 44 - LAND DEVELOPMENT CODE / Article XII - DATA CENTERS / Division 2 - SITING AND DESIGN STANDARDS
Sec. 44-264. Fencing and security.
About this text
- As published by Municode, current through 2026-09-15
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) All data centers shall be enclosed by a secure perimeter fence with a minimum height of eight feet.
(b) Fencing along public road frontages shall not be chain link, barbed wire, or razor wire.
Public-facing fencing shall incorporate one or more of the following: decorative or architectural materials such as masonry or wood (solid metal panel fencing is prohibited along public road frontages); or a vegetative buffer of sufficient density to screen the fence from public view.
(c) Fences or freestanding walls closer to a property line than the principal building setback line may not exceed 12 feet in height and shall have no barbed or razor wire. All fencing shall be black-coated or painted vinyl or metal, with slats limited to vertical placement only.
(d) Controlled access gates, security signage, and continuous on-site or remote surveillance shall be required. Each data center shall provide 24-hour emergency contact signage visible at the access entrance, including company name (if applicable), owner or representative name, telephone number, and corresponding local power company and telephone number.
(e) Along public road frontages, all perimeter fencing shall be located behind the required landscape buffer and integrated with plantings to minimize visual mass from the right-ofway.
History
(Ord. No. 26-001, 6-16-26)