McDuffie County · Zoning Ordinance
Part II - CODE OF ORDINANCES / Chapter 44 - LAND DEVELOPMENT CODE / Article XII - DATA CENTERS / Division 2 - SITING AND DESIGN STANDARDS
Sec. 44-263. Structural and design standards.
About this text
- As published by Municode, current through 2026-09-15
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) General. All principal and accessory structures shall be arranged, designed, and constructed to harmonize with the site and surrounding properties. Prefabricated, preengineered, or modular structures are permitted subject to the following:
(1) All structures shall have permanent concrete foundations.
(2) Exterior facades shall use muted earth-tone colors—including beiges, tans, greens, browns, and similar—and shall be free of visible defects, decay, or corrosion.
(3) The use of shipping containers, railroad cars, semi-truck trailers, or similar temporary storage units as any component of the facility is prohibited.
(b) Building height. Maximum building height shall not exceed 80 feet unless approved via special exception with FAA clearance.
(c) Floor area ratio. The floor area ratio (FAR) shall not exceed 0.5.
(d) Facade exposure. No facade of any data center shall have more than 20 percent of its area exposed with apparatus, including vents, fans, and HVAC systems. All mechanical equipment—whether roof- or ground-mounted—that is visible to adjacent property or roads shall be screened using opaque fences or walls. Where airflow is required, perforated brick walls or equivalent architectural treatments may be permitted.
History
(Ord. No. 26-001, 6-16-26)
Read this code where it is posted (Municode) The source is the city's code as its publisher or its own website posts it. Check it there for later changes.