McDuffie County · Zoning Ordinance
Part II - CODE OF ORDINANCES / Chapter 44 - LAND DEVELOPMENT CODE / Article XII - DATA CENTERS / Division 4 - SAFETY AND EMERGENCY STANDARDS
Sec. 44-281. Fire safety.
About this text
- As published by Municode, current through 2026-09-15
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) An active clean-agent fire suppression system must be provided and maintained in good working order within any structure containing server equipment. High-sensitivity smoke detectors shall be installed and operational to activate the system.
(b) Data centers shall install fire suppression systems appropriate for sensitive electrical equipment and meeting, at a minimum, the fire and life safety codes adopted by the county.
(c) There shall be an emergency electrical termination switch installed outside of any containment structure that contains server equipment. The switch shall be clearly and appropriately signed so that responding public safety officials can quickly identify it.
(d) All building systems required by this chapter—including heat transfer apparatuses, fire detection and suppression systems, and containment structures—shall be designed by a state licensed professional in accordance with all applicable codes and standards.
History
(Ord. No. 26-001, 6-16-26)
Read this code where it is posted (Municode) The source is the city's code as its publisher or its own website posts it. Check it there for later changes.