McDuffie County · Zoning Ordinance
Part II - CODE OF ORDINANCES / Chapter 44 - LAND DEVELOPMENT CODE / Article XII - DATA CENTERS / Division 4 - SAFETY AND EMERGENCY STANDARDS
Sec. 44-282. Temperature and worker safety.
About this text
- As published by Municode, current through 2026-09-15
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) The ambient temperature inside any containment space housing server equipment shall not exceed 120 degrees Fahrenheit at any time.
(b) No person shall be permitted to regularly inspect or work within a containment area housing server equipment if the ambient temperature within that area exceeds 90 degrees Fahrenheit, without appropriate heat protection measures in place.
(c) A written safety practices and procedures plan must be provided to the county for review, and at least one copy must be kept in every working space on the premises.
History
(Ord. No. 26-001, 6-16-26)