Sec. 5.14. Commercial hood systems.
About this text
- As published by Municode, current through 2026-06-16
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(1) Plans shall be submitted to the fire marshal's office for installation of commercial hoods. Plans must be approved before work shall begin.
(2) No commercial hood system shall be approved without passing a blow down (balloon test), a light test and a hood-to-duct test of the entire duct system conducted in accordance with the specifications of the fire marshal's office. No test will be accepted unless a representative of the fire marshal's office is present to witness the test when conducted.
(3) A representative of the fire marshal's office shall be present to witness a light test on all new installations of commercial hood exhaust systems.
The light test shall be performed by passing a lamp having a power rating of not less than 300 watts through the entire section of ductwork to be tested. The lamp shall be open so as to emit light equally in all directions perpendicular to the duct walls. The ductwork shall be permitted to be tested in sections, provided that every joint is tested.
(4) Documentation shall be provided to the fire marshal's office certifying that the commercial kitchen hood is constructed according to NFPA guidelines and that it passed a light test.
(5) Documentation shall be provided to the fire marshal's office certifying that the system is installed according to the manufacturer's instructions, NFPA guidelines, and chapter 120-3-3 and that the system is operational. The Georgia license number and installer permit number shall be provided to the fire marshal's office, and a blue tag must be on the system.
(6) Documentation of the required semiannual test on commercial hood systems shall be kept on the premises for a period of three (3) years and made available for inspection upon request.
(7) Documentation of the required cleaning of commercial hood systems shall be kept on the premises for a period of three (3) years and made available for inspection upon request.
(8) Any deficiencies in a commercial hood system that prevent the system from having a blue tag shall be repaired immediately. The fire marshal's office shall be notified within 24 hours of any commercial hood system with a red noncompliance tag.