Sec. 5.15. Fire alarm systems.

About this text

  • As published by Municode, current through 2026-06-16
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(1) Plans must be submitted to the fire marshal's office for review on new fire alarm systems and modifications to existing fire alarm systems.

(2) A representative of the fire marshal's office must be present for a final test of all new and

modified fire alarm systems.

(3) The following documents must be provided to the fire marshal's office at the time of the final test:

(a) Battery calculations for fire alarm system.

(b) Fire alarm system record of completion.

(c) Fire alarm certification letter from an installer licensed with the State of Georgia.

(d) Fire alarm certification for interconnection to auxiliary systems such as kitchen hood suppression, air handling duct detectors, smoke removal systems, elevator recall systems, and fire door release

systems.

(4) Documentation on the annual required test on fire alarm systems shall be kept on the premises for a period of three (3) years and made available for inspection upon request.

History

The history line the source prints at the end of the section.

(Ord. No. 2025-03, 6-3-2025)