Sec. 5.18. Fire department connections

About this text

  • As published by Municode, current through 2026-06-16
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(FDC).

(1) A fire hydrant shall be located within 50 feet of the fire department sprinkler connections

(FDC).

(2) A post indicator valve (PIV) shall be installed on all sprinkler systems and shall be provided with a tamper switch and lock and

shall be monitored by the fire alarm system.

(3) At least one (1) fire hydrant with a minimum flow of 1,000 gpm will be located within 250 linear feet of any newly constructed commercial occupancy where an approved water

system exists.

(4) The location of fire hydrants, fire department connections (FDC), and post indicator valves (PIV) shall be approved by the fire marshal.

History

The history line the source prints at the end of the section.

(Ord. No. 2025-03, 6-3-2025)