Sec. 5.18. Fire department connections
Sobre este texto
- As published by Municode, current through 2026-06-16
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(FDC).
(1) A fire hydrant shall be located within 50 feet of the fire department sprinkler connections
(FDC).
(2) A post indicator valve (PIV) shall be installed on all sprinkler systems and shall be provided with a tamper switch and lock and
shall be monitored by the fire alarm system.
(3) At least one (1) fire hydrant with a minimum flow of 1,000 gpm will be located within 250 linear feet of any newly constructed commercial occupancy where an approved water
system exists.
(4) The location of fire hydrants, fire department connections (FDC), and post indicator valves (PIV) shall be approved by the fire marshal.