604.4.2.1. Once-Through Cooling.
About this text
- As published by Municode, current through 2026-01-20
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Once-through cooling using potable water is
prohibited.
604.4.2.2 Cooling Towers and Evaporative Coolers. Cooling towers and evaporative coolers shall be equipped with makeup water and blow down meters, conductivity controllers and overflow alarms. Cooling towers shall be equipped
with efficiency drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counterflow towers and 0.005 percent for crossflow towers.