Coweta County · Code of Ordinances

Part II - CODE OF ORDINANCES / Chapter 78 - UTILITIES / Article VI - BACKFLOW PREVENTION BY CONTAINMENT

Sec. 78-95. Water from other sources and fire hydrants.

About this text

  • As published by Municode, current through 2026-05-19
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(1) When any premises is served by the Coweta County Water and Sewer Department, and the owner of said premises continues to have a well or any other source of water, it shall be in violation of these procedures for the plumbing on said premises to be installed or so interconnected that water in the Coweta County Water and Sewer Department and the private water supply can, in any way, become intermingled.

(2) Upon discovery of an uncontrolled interconnection on any premises being furnished water through the county water system, as in item (1) above, the owner of said premises shall be notified that the interconnection must be removed or controlled by a backflow-prevention device within 30 days, and that failure to remove or correct the interconnection will result in removal of the meter. If the correction is not made within the 30-day period, the meter will be removed and will not be reinstalled until the maximum-type backflow protection is installed at the service-connection, and the owner has paid for all associated costs.

(3) Booster pumps installed on the service line to or within any premises, must be approved and permitted by the Coweta County Water and Sewer Department, and such permitted pumps shall be equipped with a low-pressure cut-off device designed to shut off the booster pump when the pressure in the service line on the suction side of the pump drops to 20 PSI or below. It shall be the duty of the water consumer to maintain their low-pressure cut-off device in proper working order at all times and to certify to the Coweta County Water and Sewer Department, at least once a year, that the device is operable.

NOTE: Consumer shall assume all liabilities.

(4) Tanks, tanker trucks, seed spraying trucks, and other containers that will be filled with water obtained under the "fire hydrant water use permit" policy must be inspected, approved, and permitted by the county water and sewer department for the permanent installation of an approved air gap or reduced pressure zone backflow-prevention device prior to issuance of the fire hydrant water use permit. In addition, connecting hoses, etc., to a fire hydrant for purposes other than filling an approved tank or tank truck shall also include, as a minimum, a prior approved and inspected double check valve backflow preventer.