Part II - CODE OF ORDINANCES / Chapter 78 - UTILITIES / Article VI - BACKFLOW PREVENTION BY CONTAINMENT
Sec. 78-96. Selection of devices.
About this text
- As published by Municode, current through 2026-05-19
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(1) Vacuum breakers and backflow preventers shall be selected on basis of the impurities involved and the type cross-connection. The impurities shall be classified as contaminants (hazardous) and pollutants (non-hazardous): the type cross-connection by whether it is non-pressure or pressure as follows: (See Terminology: Appendix B).
(a) Cross-connection, non-pressure type. This type of connection, when not protected by a minimum air gap, shall be protected by an appropriate vacuum breaker or an
appropriate backflow preventer (BFP).
(b) Cross-connection pressure type. This type connection shall be protected by an appropriate BFP only.
CAUTION: A pressure vacuum breaker shall not be used alone on a pressure-type cross-connection.
NOTE: Because an irrigation system serves an environment that is open to atmosphere, it would not be classified as a pressure-type cross-connection. However, due to the special nature of the installation, minimum protection against backflow shall include a double check valve backflow preventer. If chemicals are injected into the system, minimum protection shall include a reduced pressure zone backflow preventer.
Section 1105.7, Georgia State Plumbing Code.
As of the effective date of this article, any lawn irrigation shall require a separate tap, meter and backflow preventer purchased from and installed by the Coweta County Water and Sewer Department. No more domestic/lawn irrigation combination systems shall be allowed. Any combination lawn irrigation systems installed after this date shall be considered a penalty and subject to provisions as set forth in section 78-93 of this chapter.
(2) Vacuum breakers shall be corrosion resistant. Other backflow-prevention devices, including accessories, components, and fittings in sizes two inches and smaller shall be bronze with threaded connections. Sizes 21
/2 inches and larger shall be bronze, or fused epoxy-coated iron inside and out, or galvanized iron, with flanged connections.
(3) Each device shall have a brass identification tag, securely attached with corrosionresistant mechanical fasteners, and include the manufacturer's name, serial number, and maximum working pressure and temperature.
History
(Ord. of 11-15-05)