Part II - CODE OF ORDINANCES / Chapter 78 - UTILITIES / Article VI - BACKFLOW PREVENTION BY CONTAINMENT
Sec. 78-96. Selection of devices.
Sobre este texto
- As published by Municode, current through 2026-05-19
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
(1) Vacuum breakers and backflow preventers shall be selected on basis of the impurities involved and the type cross-connection. The impurities shall be classified as contaminants (hazardous) and pollutants (non-hazardous): the type cross-connection by whether it is non-pressure or pressure as follows: (See Terminology: Appendix B).
(a) Cross-connection, non-pressure type. This type of connection, when not protected by a minimum air gap, shall be protected by an appropriate vacuum breaker or an
appropriate backflow preventer (BFP).
(b) Cross-connection pressure type. This type connection shall be protected by an appropriate BFP only.
CAUTION: A pressure vacuum breaker shall not be used alone on a pressure-type cross-connection.
NOTE: Because an irrigation system serves an environment that is open to atmosphere, it would not be classified as a pressure-type cross-connection. However, due to the special nature of the installation, minimum protection against backflow shall include a double check valve backflow preventer. If chemicals are injected into the system, minimum protection shall include a reduced pressure zone backflow preventer.
Section 1105.7, Georgia State Plumbing Code.
As of the effective date of this article, any lawn irrigation shall require a separate tap, meter and backflow preventer purchased from and installed by the Coweta County Water and Sewer Department. No more domestic/lawn irrigation combination systems shall be allowed. Any combination lawn irrigation systems installed after this date shall be considered a penalty and subject to provisions as set forth in section 78-93 of this chapter.
(2) Vacuum breakers shall be corrosion resistant. Other backflow-prevention devices, including accessories, components, and fittings in sizes two inches and smaller shall be bronze with threaded connections. Sizes 21
/2 inches and larger shall be bronze, or fused epoxy-coated iron inside and out, or galvanized iron, with flanged connections.
(3) Each device shall have a brass identification tag, securely attached with corrosionresistant mechanical fasteners, and include the manufacturer's name, serial number, and maximum working pressure and temperature.
Historia
(Ord. of 11-15-05)