A. Distribution system.
1. Each section of reuse pipe, shall be painted with Pantone 522C or 512C or other shade of purple accepted by the county over a
minimum of 60 percent of the circumference of the pipeline except for any distinguishing marks of manufacture or product information which shall remain visible and unpainted.
2. Reuse water piping shall be wrapped in a Pantone 522C polyethylene tube wrap
where required for cathodic protection
(ANSI/AWWA C105/A21.5).
3. During the installation of the reuse water piping, a three-inch-wide tape to say "REUSE WATER-NONPOTABLE" (purple with white or black lettering) is to be
installed two inch above the line during installation.
4. Reuse water pipe must maintain three feet horizontal separation and 18 inches vertical separation from both proposed
and existing sanitary sewer force mains and water mains. Unless approved by the Hall County Public Works and Utilities Director, no person shall construct any reuse pipe or conduit for reuse water in any street within four feet on each side of the centerline of any sewer.
5. All reuse water valves shall have square valve boxes with the words "RECLAIMED
WATER" cast in the lid. All boxes must be painted on the inside and lid with Pantone 522C or 512 or other shade of purple
accepted by the county. Valve boxes shall be Russco C2503 6.5" square. Standard
round valve boxes are prohibited in the nonpotable reuse system.
6. All valves must be marked with a purple drivable marker 78 inches long and extend to the valve. The markers are not to protrude the finished surface grade more than three feet and no less than 18 inches above the finished grade. There must be a label on both sides of the marker with the following information: "REUSE WATER
VALVE, DO NOT TAP, NON-POTABLE,
BEFORE DIGGING CONTACT HALL
COUNTY PUBLIC WORKS AND UTILITIES, PHONE # 770-531-6800."
7. There shall be no physical connection between the reuse system and any other
water supply. An isolation valve does not constitute a separation.
8. Reuse water may only be connected to "in the ground" sprinkler systems or to a
nonstandard hose bib located within a lockable meter box only where specifically approved by the county in the end reuse
user agreement.
9. No aboveground irrigation system using reuse water will be approved on residential sites.
10. All piping and pipelines carrying reuse water shall be color-coded Pantone Purple 522C using sunlight stable pigment.
11. All valves, hose bibs where allowed, and outlets shall be tagged and color-coded
purple to differentiate reuse water from potable water. All reuse water valves and outlets shall be appropriately tagged or labeled "Do Not Drink" together with the equivalent standard international symbol to warn the public and employees that the water is not intended for drinking.
12. Where hose bibs are allowed, nonstandard hose connections shall be used to preclude the interchange of hoses with
the potable water system. Hose bibs are prohibited from residential customer sites.
13. Hose bibs must be installed underground within a lockable meter box. Cam Lock
connection assemblies in small sizes (onehalf to three-quarter-inch) with lockable meter boxes will be required on all hose connections designated for reuse water.
14. Reuse water irrigation systems shall be designed, constructed and operated so as to minimize over spray onto impervious
surfaces.
15. Runoff of reuse water into ditches or streams is prohibited.
16. Low trajectory nozzles, or other means to minimize aerosol formation, shall be used within 100 feet of outdoor public eating, drinking and bathing facilities. Irrigation systems should be designed so that spray does not go outside of the established
boundaries.
17. All sites utilizing reuse water for irrigation such as golf courses, residential developments, parks and other public areas, are required to post visible signs at all entrance locations notifying the public of reuse water.
B. New service installations/meters and meter boxes.
1. Reuse meters must be a badger meter for reuse water, measuring in gallons consumed. To ensure identification of reuse water meters, the international color of Pantone 522C is located on the lid of the register. The register face, lid, shroud and meter bottom and the word "REUSE" is
marked on the brass housing.
2. All reuse meters will be installed in a Carson-Brooks Plastics box. Meter box
lids will be purple colors 1419, 1220 or 1324 and labeled "REUSE WATER".
3. All reuse meter installations must maintain a minimum of three feet from the potable water meter.
C. Drawings. As-built drawings shall be provided to Hall County Public Works and Utilities upon completion of each phase of installation showing valve locations, storage ponds, tap locations, and size of taps.
D. Storage ponds. A reuse user may store reuse water on his property in a storage pond that is constructed and maintained in accordance with all standards for the same in local, state and federal law including any such standards set forth in the publications listed in section 13.20.040B. of this chapter.
History
(Res. of 1-8-09(2), §§ 1, 2(Exh. A))
Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.