Part - CODE OF ORDINANCES / Chapter 18 - FIRE PREVENTION AND PROTECTION / Article III - FIRE PROTECTION REGULATIONS / Division 2 - CONSTRUCTION SPECIFICATIONS

Sec. 18-84. Hydrant standards.

About this text

  • As published by Municode, current through 2023-06-06
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) Hydrants, fittings, valves, and fire department connections shall be approved by the county fire chief. Fire department connections shall be not less than 18 inches or more than 36 inches above the level of the adjoining ground or paving. The thread of such connections shall be uniform with that used by the fire department.

(b) Hydrants shall meet the requirements of NFPA No. 24, fire hydrants for outside protection, and have not less than four-inch connection with the mains. The number, size and arrangement of the outlets, the size of the main valve opening and the size of barrel shall be suitable for protection to be provided and shall be approved by the fire chief.

(c) For average conditions hydrants should be placed 50 feet from the buildings protected.

Where it is impossible to place them at this distance, they may be put nearer provided they are set in locations where the chance of injury by falling walls is minimized and from which men are not likely to be driven by smoke or heat.

(d) The size and shape of the operating nut and the direction the hydrant stem operates shall be uniform throughout the county.