Haralson County · Code of Ordinances

Part - CODE OF ORDINANCES / Chapter 18 - FIRE PREVENTION AND PROTECTION / Article III - FIRE PROTECTION REGULATIONS / Division 2 - CONSTRUCTION SPECIFICATIONS

Sec. 18-83. Water main standards and hydrant spacing.

About this text

  • As published by Municode, current through 2023-06-06
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) In single-family approved subdivisions, at least six inch pipe shall be installed, four-inch pipe to be used when it constitutes a good gridiron and then only up to 600 feet in length between interconnecting mains. Fire hydrants shall be spaced not to exceed 600 feet. Two-way hydrants may be used in single-family subdivisions.

(b) In multifamily residential subdivisions or multifamily apartment complexes, at least six-inch or larger pipe shall be installed, four-inch pipe to be used when it constitutes a good gridiron and then only up to 600 feet in length between interconnecting mains. Fire hydrants shall be two-way hydrants and shall be spaced not to exceed 500 feet with additional fire hydrants located as necessary to permit all portions of buildings to be reached by hose lays of not more than 600 feet.