Sec. 16-99. Nonresidential construction.

About this text

  • As published by Municode, current through 2024-07-09
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(a) New construction or the substantial improvement of any structure located in A1-30, AE, or AH zones, may be floodproofed in lieu of elevation. The structure, together with attendant utility and sanitary facilities, must be designed to be watertight to one foot above the base flood elevation, with walls substantially impermeable to the passage of water, and structural components having the capability of resisting hydrostatic and hydrodynamic loads and the effect of buoyancy.

(b) A registered professional engineer or architect shall certify that the design and methods of construction are in accordance with accepted standards of practice for meeting the provisions above and shall provide such certification to the official as set forth above and in section 16-48(7).

History

The history line the source prints at the end of the section.

(Ord. No. 001-10, art. 4, § B(2), 8-10-2010)