Part - CODE OF ORDINANCES / Chapter 66 - UTILITIES / Article II - WATER / Division 2 - BACKFLOW PREVENTION

Sec. 66-63. Fire sprinkler systems.

About this text

  • As published by Municode, current through 2026-04-07
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

All unmetered fire sprinkler systems without booster facilities or chemical additives must have a double check-detector checkvalve assembly as a minimum containment device. The detector meter assembly shall meet the requirements contained in the water and wastewater system standards for the county. All unmetered fire sprinkler systems with a booster facility or chemical additives must have a reduced pressure principle detector assembly as a minimum containment device.

History

The history line the source prints at the end of the section.

(Ord. of 2-1-2000, § 1.08)