Part - CODE OF ORDINANCES / Chapter 66 - UTILITIES / Article II - WATER / Division 2 - BACKFLOW PREVENTION
Sec. 66-63. Fire sprinkler systems.
Sobre este texto
- As published by Municode, current through 2026-04-07
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.
All unmetered fire sprinkler systems without booster facilities or chemical additives must have a double check-detector checkvalve assembly as a minimum containment device. The detector meter assembly shall meet the requirements contained in the water and wastewater system standards for the county. All unmetered fire sprinkler systems with a booster facility or chemical additives must have a reduced pressure principle detector assembly as a minimum containment device.
Historia
(Ord. of 2-1-2000, § 1.08)