Paulding County · Code of Ordinances
Part II - CODE OF ORDINANCES / Chapter 74 - WATER / Article II - CONTROL OF BACKFLOW AND CROSS CONNECTIONS
Sec. 74-44. Installation of devices.
About this text
- As published by Municode, current through 2025-12-09
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(a) Vacuum breakers. Vacuum breakers shall be installed with the critical level at least six inches above the flood level rim of the fixture they serve and on the discharge side of the last control valve to the fixture. No shutoff valve or faucet shall be installed beyond the vacuum breaker. For closed equipment or vessels such as pressure sterilizers, the top of the vessel shall be treated as the flood level rim, but a check valve shall be installed on the discharge side of the vacuum breaker.
(b) Reduced pressure principle backflow preventer. A reduced pressure principle type backflow preventer may be installed subject to full static pressure.
(c) Devices of all types. Backflow and backsiphonage preventing devices shall be accessibly located preferably in the same room with the fixture they serve. Installation in utility or service spaces, provided they are readily accessible, is also permitted.
History
(Code 1987, § 5-133)
Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.