Sec. 38-92. Specific standards.

About this text

  • As published by Municode, current through 2026-09-08
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

In all areas of special flood hazard where base flood elevation data has been provided as set forth in section 38-38 or section 38-65, the following provisions are required:

(1) Residential construction. New construction or substantial improvement of any residential structure (including a manufactured home) shall have the lowest floor, including the basement, elevated to no

lower than two feet above the base flood elevation. Should solid foundation perimeter walls be used to elevate a structure, openings sufficient to facilitate the unimpeded movements of floodwaters shall be provided in accordance with the standards of subsection (3) of this section.

(2) Nonresidential construction. New construction or substantial improvement of any commercial, industrial or other nonresidential structure (including manufactured homes) shall either have the lowest floor, including the basement, elevated to

no lower than two feet above the level of the base flood elevation or, together with attendant utility and sanitary facilities, be floodproofed so that below the base flood level the structure is watertight with walls substantially impermeable to the passage of water and with structural components having the capability of resisting hydrostatic and hydrodynamic loads and

effects of buoyancy.

a. A registered professional engineer or architect shall develop and/or review the structural design, specifications, and plans for the construction, and shall certify that the design and methods of construction are in accordance with the accepted standards of practice for meeting the applicable provisions of section 38-64(2).

b. Where floodproofing is utilized for a particular structure in accordance with this section or section 38-93(2), then a registered, professional engineer or architect shall certify that the floodproofing methods are adequate to withstand the flood depths, pressures, velocities, impact and uplift forces and other factors associated with the base flood. Such certification, including an indication of the specific elevation (in relation to

mean sea level) to which structures are floodproofed shall be provided to and manufactured by the official as set forth in section 38-64(2).

(3) Elevated buildings. New construction or substantial improvements of elevated buildings that include fully enclosed areas formed by foundation and other exterior walls below the base flood elevation shall be designed to preclude finished

living space and designed to allow for the entry and exit of floodwaters to automatically equalize hydrostatic flood forces on exterior walls.

a. Designs for complying with this requirement must be certified by a professional engineer or architect or

meet the following minimum criteria:

1. Provide a minimum of two openings having a total net area of not less than one square inch

for every square foot of enclosed area subject to flooding;

2. The bottom of all openings shall be no higher than one foot above grade; and

3. Openings may be equipped with screens, louvers, valves or other coverings or devices provided they permit the automatic flow of floodwaters in both direction.

b. Electrical, plumbing, and other utility connections are prohibited below the base flood elevation.

c. Access to the enclosed area shall be the minimum necessary to allow for parking of vehicles (garage door) or limited storage of maintenance equipment used in connection with the premises (standard exterior door) or

entry to the living area (stairway or elevator).

d. The interior portion of such enclosed area shall not be partitioned or finished into separate rooms.

History

The history line the source prints at the end of the section.

(Ord. No. 87-2, art. 5, § B, 8-4-1987)