Whitfield County · Code of Ordinances
Chapter 14 - SITE DESIGN / Article V - UTILITIES
Sec. 14-65. Wellhead protection areas.
About this text
- As published by Municode, current through 2026-05-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
Every wellhead protection area consists of two zones, as follows:
(1) The control zone shall be a circle outward from the well bore, with a radius of 15 feet for impervious surface material, such as concrete, or a radius of 25 feet for permeable surface material. Within the control zone, activities shall be restricted so that
there are minimal sources of potential pollution in the immediate vicinity of the well bore. Only chemicals used for water treatment may be stored in this zone.
Motor fuels, oil, motor vehicles, or portable equipment powered by an internal combustion engine shall not be stored in
the control zone. On-site fuel storage for auxiliary power shall have a spill containment system for the entire volume of fuel.
This zone will be protected by a chain-link fence (or equivalent) having a minimum height of seven feet and access shall be through a locking gate (or equivalent.)
Chemicals or motorized vehicles may be used for maintenance of the well, well house, pump, or associated plumbing. The control zone elevation is required to be at least one foot above the 500-year flood elevation from any surface drainage source or underground drainage source under the influence of surface water.
(2) The management zone is divided into the inner management zone and the outer management zone. Wells drawing water only from confined aquifers will have an inner management zone extending outward from the center of the well bore or spring head for a radius of 100 feet. Wells
drawing water from unconfined aquifers, except those lying areas of karst, will have an inner management zone extending outward from the center of the well bore or spring head for a radius of 250
feet. Wells drawing water from unconfined aquifers identified as being in areas of karst, will have an inner management
zone extending outward from the center of the well bore or spring head for a radius of 500 feet. The outer management zone shall be determined as follows: Wells drawing water only from confined aquifers are not required to have an outer management zone. Wells drawing water from unconfined aquifers identified as being in
areas of karst, will have an outer management zone determined by hydrological mapping. Wells drawing water from unconfined aquifers utilizing fractured crystalline rock aquifers will have an outer management zone determined according to the "Health Method Curve" contained in the
EPA approved Georgia Wellhead Protec- tion Plan. Other wells not meeting the above criteria will have their outer management zones determined by time of travel calculations (minimum of a five-year time
of travel) or by volumetric calculations as appropriate. The following may not be located within either the inner zone or outer zone:
(a) Solid waste, industrial or construction/demolition landfills;
(b) Land disposal of hazardous waste;
(c) Land application of wastewater or sludge;
(d) Underground injection wells;
(e) Wastewater treatment basins without impermeable synthetic liners, and
(f) Abandoned underground storage tanks not meeting the standards of Georgia DNR Code section 391-3- 15-11 of the Rules for Underground Storage Tanks.
The following may not be located within the inner zone:
(a) Environmental facilities with no releases to the ground (except to sanitary sewer lines);
(b) Environmental facilities determined that any release to the ground that will not be a threat to public health and safety (an example is one or two domestic septic systems);
(c) Underground storage tanks;
(d) Non-domestic septic tanks with drain fields, and
(e) Animal feedlots, poultry enclosures or animal enclosures (not construed to apply to family pets).
The following may be located within either the inner zone or outer zone:
(a) Facilities permitted to handle, treat, store or dispose of hazardous waste or materials which has an impermeable pad having a spill and leak collection system. All such activities
must be performed on this pad,
(b) Agricultural waste impoundments having an impermeable synthetic liner, and
(c) Quarries or underground mines having had a hydrogeological investigation (carried out by a professional engineer or geologist) demonstrating
that the operation will not pollute the well or spring or cause a reduction of ground water flow to the well or spring.
The following may be located within the outer zone:
(a) wastewater treatment basins with impermeable synthetic liners,
(b) underground storage tanks meeting the highest standards applicable under Georgia DNR Code section Underground Storage Tank Act, and
(c) abandoned underground storage tanks meeting the standards of Georgia DNR Code section 391-3-15-.11 of the Rules for Underground Storage Tanks.
History
(Res. of 6-9-03, § 5-5)
Read this code where it is posted (Municode) The source is the county's code as its publisher or its own website posts it. Check it there for later changes.