Chapter 5 - BUILDINGS, CONSTRUCTION AND RELATED ACTIVITIES / Article I - BUILDING ORDINANCE / Division 3 - FIRE HYDRANT AND WATER SUPPLY REQUIREMENTS

Sec. 5-32. Installation of water mains.

About this text

  • As published by Municode, current through 2026-05-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

(1) In accordance with the Rules and Regulations of the Safety Fire Commissioner, Chapter 120-3-3, Rules and Regulations

for the State Minimum Fire Safety Standards; (a) No water main less than eight inches in diameter shall be installed to

supply more than one fire hydrant or one hydrant on dead-end mains over 500 feet.

(b) No pipe smaller than eight inches in diameter shall be used to supply one hydrant and automatic extinguishing systems. (c) No pipe smaller than eight inches in diameter shall be installed to supply

more than one hydrant and automatic extinguishing systems on looped mains over 1,000 feet. (Exception: other installations, new or existing, acceptable to and approved by the authority having jurisdiction, the approval shall include a letter from the local responding fire department. Note: Pipe sizing should be based upon sound engineering practices based

upon projected water demand, fire fighting capabilities, and water supply characteristics. Whitfield County may require any larger diameter water main as reasonably warranted by engineering or geographical conditions, or as specified by Dalton Utilities to meet the required fire

flows.)

(a) Reasonable effort shall be made to establish a gridiron layout, preferably "looped" with a minimum of deadend lines;

(b) Additional water mains added to existing infrastructure shall be engineered and installed so as to provide the needed gallons per minute (hereinafter "GPM") fire flow per type of development or structures to be protected, per Insurance Services Office, Guide for Determination of Needed Fire Flow, as summarized

herein below.

(2) Water mains installed in all residential subdivisions shall provide, at a minimum, 500 GPM at fire hydrants if structures are 100 feet or more apart, from corner to corner at the closest points. Water mains in such areas where structures are 31 to 99 feet apart must provide not less than 750 GPM; structures spaced 11 to 30 feet apart shall require 1,000 GPM; and struc- tures ten feet or less shall require 1,500 GPM, calculated at fire hydrants within 500 feet of hose lays from such structures.

(3) Water mains installed for all manufacturing or commercial uses shall provide not less than the necessary fire flow per structure type. The needed fire flow shall be determined by the Insurance Services Office, Guide For Determination of Needed Fire Flow. Fire flow supply calculation

shall include total flow of hydrants within 1000 feet of structures.

(4) Approval for the type and grade of water pipe to be installed pursuant to this section shall be given by Whitfield County.

All water pipe, valves, hydrants, fittings, and other appurtenances will be installed in accordance with Dalton Utilities standard specifications and requirements.

(5) No person subject to this section shall construct or cause to be constructed any structure upon the lot or parcel until water mains and fire hydrants thereon shall have been installed and approved by Dalton Utilities and determined to be in operable condition for fire fighting by the Whitfield County Fire Chief.

History

The history line the source prints at the end of the section.

(Ord. of 11-28-05; Ord. of 2-13-06)