Whitfield County · Code of Ordinances
Chapter 5 - BUILDINGS, CONSTRUCTION AND RELATED ACTIVITIES / Article I - BUILDING ORDINANCE / Division 3 - FIRE HYDRANT AND WATER SUPPLY REQUIREMENTS
Sec. 5-33. Installation of fire hydrants.
About this text
- As published by Municode, current through 2026-05-11
- The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.
(1) Fire hydrants serving all manufacturing or commercial structures, hospitals, medical care facilities, nursing homes, offices, schools, educational facilities, apartments, condominiums, and multifamily residential structures shall be spaced
not more than 600 feet from the next fire hydrant such that no part of any such structure shall be more than 300 feet from a fire hydrant.
(2) Fire hydrants shall be spaced not more than 1,000 feet from the next fire hydrant within single-family or dual-family residentially zoned or used areas. Any person subject to this section shall install primary fire hydrants as close to roadway intersections as practicable, placing intermediate fire hydrants along a public right-ofway to maintain the required minimum fire hydrant spacing set forth herein.
(3) No fire hydrant shall be used for any purpose other than fire fighting purposes without approval of Dalton Utilities.
History
(Ord. of 11-28-05)