An automatic sprinkler system shall be provided throughout buildings containing a Group M. occupancy where one of the following conditions exists:
1. A Group M fire area exceeds 12,000 square feet (1115 m2 ).
2. A Group M fire area is located more than three stories above grade plane.
3. The combination area of all Group M fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2
).
4. A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeds 5,000 square feet (464 m2 ).
Replace the previous text of 903.2.7 with the following: