Part II - CODE OF ORDINANCES / Chapter 30 - FIRE PREVENTION AND PROTECTION / Article III - FIRE CODE

903.2.7. Group M.

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

An automatic sprinkler system shall be provided throughout buildings containing a Group M. occupancy where one of the following conditions exists:

1. A Group M fire area exceeds 12,000 square feet (1115 m2 ).

2. A Group M fire area is located more than three stories above grade plane.

3. The combination area of all Group M fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2

).

4. A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeds 5,000 square feet (464 m2 ).

Replace the previous text of 903.2.7 with the following: