An automatic sprinkler system shall be provided throughout buildings containing a Group M. occupancy where one of the following conditions exists:

1. A Group M fire area exceeds 4,999 square feet (464.4222 m2 ).

2. A Group M fire area is located more than three stories above grade plane.

3. The combination area of all Group M fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929.030 m2 ).

4. A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeds 4,999 square feet (464.4222 m2 ).