An automatic sprinkler system shall be provided throughout buildings containing a Group M. occupancy where one of the following conditions exists:
1. A Group M fire area exceeds 4,999 square feet (464.4222 m2 ).
2. A Group M fire area is located more than three stories above grade plane.
3. The combination area of all Group M fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929.030 m2 ).
4. A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeds 4,999 square feet (464.4222 m2 ).
(6) Modify the adopted Georgia State Minimum Standard Fire Code 903.2.9 of the International Fire Code from: