An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists:

1. A Group S-1 fire area exceeds 12,000 square feet (1115 m2 ).

2. A Group S-1 fire area is located more than three stories above grade plane.

3. The combination area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2

).

4. A Group S-1 occupancy used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m2 ).

5. A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m2

).

Replace the previous text of 903.2.9 with the following: