An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists:

1. A Group S-1 fire area exceeds 4,999 square feet (464.4222 m2 ).

2. A Group S-1 fire area is located more than three stories above grade plane.

3. The combination area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929.030 m2

).

4. A Group S-1 occupancy used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m2 ).

5. A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m2

).

(7) Modify the adopted Georgia State Minimum Fire Code NFPA 101 to add the following:

Any reference to a square footage requirement for the installation of an automatic sprinkler system in chapter 12 through 43 shall be amended to require automatic sprinklers installed in structures over 4,999 square feet.

Existing exemptions referenced in the adopted International Fire Code shall be applicable to this modification.

(8) Modify the adopted Georgia State Minimum Standard Fire Code 230.7(A)(l) of the National Electrical code from:

230.7(A)(l) Readily Accessible Location. The service disconnecting means shall be installed at a readily accessible location either outside of a building or structure or inside nearest the point of entrance of the service conductors.

Replace the previous text of 230.70(A)(l) with:

230.70(A)(l) Readily Accessible Location. The service disconnecting means shall be installed at a readily accessible location outside of a building or structure nearest the point of entrance of the service conductors.

History

The history line the source prints at the end of the section.

(Ord. No. 2023-13, § 1, 7-10-2023; Ord. No. 2024-21, § 1, 8-5-2024)

Meetings that refer to this section

Found 1: meetings of this government whose minutes or machine transcripts name this section, or an ordinance in its history line, newest first. Found by rule from those records' own words. A reference is a pointer to another record, not a statement that the section applies or was changed.

Read this code where it is posted (Municode) The source is the city's code as its publisher or its own website posts it. Check it there for later changes.

Version local-code:jasper/code/part-ii-chapter-30-article-iii-903.2.9@2026-11-11-f563b5a684

The assistant can say what this section says in this edition, quoting it and linking to it. It will not apply the law to your situation, and nothing here is legal advice.

Jasper Code of Ordinances, 903.2.9 (Part II, Chapter 30, Article III). Group S-1 | Georgia Commons