903.2.9. Group S-1

Sobre este texto

  • As published by Municode, retrieved 2026-11-11
  • The enacted text only: the publisher's notes (editor's notes, state law references, cross references) are not included.

Las notas de arriba, el texto de la sección y su línea de historia se muestran en inglés, tal como los publica la fuente y como los da el corpus.

An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists:

1. A Group S-1 fire area exceeds 4,999 square feet (464.4222 m2 ).

2. A Group S-1 fire area is located more than three stories above grade plane.

3. The combination area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet (929.030 m2

).

4. A Group S-1 occupancy used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m2 ).

5. A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m2

).

(7) Modify the adopted Georgia State Minimum Fire Code NFPA 101 to add the following:

Any reference to a square footage requirement for the installation of an automatic sprinkler system in chapter 12 through 43 shall be amended to require automatic sprinklers installed in structures over 4,999 square feet.

Existing exemptions referenced in the adopted International Fire Code shall be applicable to this modification.

(8) Modify the adopted Georgia State Minimum Standard Fire Code 230.7(A)(l) of the National Electrical code from:

230.7(A)(l) Readily Accessible Location. The service disconnecting means shall be installed at a readily accessible location either outside of a building or structure or inside nearest the point of entrance of the service conductors.

Replace the previous text of 230.70(A)(l) with:

230.70(A)(l) Readily Accessible Location. The service disconnecting means shall be installed at a readily accessible location outside of a building or structure nearest the point of entrance of the service conductors.

Historia

La línea de historia que la fuente imprime al final de la sección.

(Ord. No. 2023-13, § 1, 7-10-2023; Ord. No. 2024-21, § 1, 8-5-2024)

Reuniones que se refieren a esta sección

Encontradas: 1. Son reuniones de este gobierno cuyas actas o transcripciones automáticas nombran esta sección, o una ordenanza de su línea de historia, de la más reciente a la más antigua. Halladas por regla a partir de las propias palabras de esos registros. Una referencia es un enlace a otro registro, no una afirmación de que la sección se aplica o se cambió.

Leer este código donde se publica (Municode) La fuente es el código de la ciudad tal como lo publica su editorial o su propio sitio web. Consúltelo allí para ver cambios posteriores.

Versión local-code:jasper/code/part-ii-chapter-30-article-iii-903.2.9@2026-11-11-f563b5a684

El asistente puede decir lo que dice esta sección en esta edición, citándola y enlazándola. No aplicará la ley a su situación, y nada de esto es asesoría legal.