A. The City of Canton reserves the right to make any changes in these requirements as may be deemed necessary. The design of the lift station shall be based on the future build out of the drainage basin upstream of the station.

B. Lift stations having a capacity less than 500 gpm (per pump) shall utilize two submersible centrifugal pumps each having a capacity of the design flow.

C. Lift stations having a capacity of 500 gpm or greater shall be reviewed on an individual basis and may have requirements differing from those outlined herein.

D. Grinder-type centrifugal pumps shall be used for pumps with a capacity of 100 gpm or less.